48
Basic Operating Procedure
Section 1-9
Creating I/O Tables for
Serial Communications
Units
I/O tables must be created for Serial Communications Units. Create the I/O
table using a Programming Device, such as a Programming Console or CX-
Programmer.
Setting the Setup Area in
the DM Area
Set the serial communications mode and the communications specifications
for the Board or Unit. Use a Programming Device, such as a Programming
Console or CX-Programmer, or the CX-Protocol to set the Setup Area.
Host Link Communications
The following table shows the default (standard) settings for Host Link com-
munications.
m = 100
×
unit number
1:1 Host Link Mode
Example: When using a Serial Communications Board/Unit with Unit Ver. 1.2
or later, host computer programs that were created using the earlier models
C500-LK101, C500-LK201, C500-LK103, or C500-LK203 can be executed
using 1:1 Host Link protocol.
m = 100
×
unit number
Protocol Macros
The following table shows the default (standard) settings for protocol macros.
m = 100
×
unit number
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit
Setting
Meaning
Port 1
Port 2
Port 1
Port 2
D32000
D32010
m
m+10
15
0
Start bit:
1 bit
Data length: 7 bits
Parity:
Even
Stop bits:
2 bits
Baud rate: 9,600 bps
08 to 11
5
Host Link mode
D32001
D32011
m+1
m+11
00 to 03
0
The baud rate setting is disabled when the
default settings are used.
D32002
D32012
m+2
m+12
15
0
Send delay: 0 ms
D32003
D32013
m+3
m+13
15
0
CTS control: No
00 to 07
00
Host Link unit number: 0
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit
Setting
Meaning
Port 1
Port 2
Port 1
Port 2
D32003
D32013
m+3
m+13
14
1
1:N/1:1 Host Link setting: 1:1 Host Link
D32003
D32013
m+3
m+13
10-08
3 hex
Host Link compatible device mode: C mode
(C500/120)
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit
Setting
Meaning
Port 1
Port 2
Port 1
Port 2
D32000
D32010
m
m + 10
15
0
Start bit:
1 bit
Data length: 7 bits
Parity:
Even
Stop bits:
2 bits
Baud rate: 9,600 bps
11 to 08
6
Protocol Macro mode
D32001
D32011
m + 1
m + 11
03 to 00
0
9,600 bps when the default settings are
used.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...