172
Auxiliary Area and CIO Area Allocations
Section 5-3
Protocol Status Area
Name
Address
Meaning
Timing
Initialize
ON
OFF
Protocol
Macro Exe-
cuting Flag
Board:
CIO 190915 (port 1)
CIO 191915 (port 2)
Unit:
n + 9 bit 15 (port 1)
n + 19 bit 15 (port 2)
This flag is turned ON when a PMCR(260)
instruction (sequence) is executed. The flag
remains OFF when execution fails.
When the sequence is completed and
receive data is written, the flag is turned OFF
after all the receive data has been written to
I/O memory.
This flag is turned OFF when the sequence
is completed (either when it is ended by End,
or when it is ended by Abort).
When the scan response notification method
is set for the sequence, first a check is made
to see if the received data has been written
to I/O memory before the Protocol Macro
Executing Flag is turned OFF.
Startup
(see note)
When
command
is exe-
cuted
When
command
has fin-
ished exe-
cuting
Step Error
Processing
Flag
Board:
CIO 190914 (port 1)
CIO 191914 (port 2)
Unit:
n + 9 bit 14 (port 1)
n + 19 bit 14 (port 2)
This flag is turned ON when a step has
ended abnormally. It is turned OFF if the
step ends normally as a result of a retry.
1: Step ended abnormally
0: Step ended normally
Startup
(see note)
When veri-
fication
error
occurs
after
receiving
When
sequence
starts
Abort Flag
Board:
CIO 190913 (port 1)
CIO 191913 (port 2)
Unit:
n + 9 bit 13 (port 1)
n + 19 bit 13 (port 2)
This flag is turned ON when processing is
ended using the Abort Switch from the user
program. When the Abort Switch is turned
ON at the end of a sequence, the sequence
may end with either End or Abort status.
Startup
(see note)
When a
forced
abort
occurs
When
sequence
starts
Tracing Flag
Board:
CIO 190912 (port 1)
CIO 191912 (port 2)
Unit:
n + 9 bit 12 (port 1)
n + 19 bit 12 (port 2)
Depending on the instruction from the CX-
Protocol, this flag is turned ON while time-
series data for send and receive messages
is being traced.
Startup
(see note)
When
trace
begins
When
sequence
starts
Sequence
End Com-
pletion Flag
Board:
CIO 190911 (port 1)
CIO 191911 (port 2)
Unit:
n + 9 bit 11 (port 1)
n + 19 bit 11 (port 2)
This flag is turned ON when a sequence is
completed for the next process or for an error
process with an END command.
When a sequence has ended normally, set-
ting END (ABORT when the sequence has
ended abnormally) enables this flag to be
used to determine whether or not the
sequence execution has ended normally.
1: Sequence ended
0: Sequence not ended
When
sequence
ends.
When
sequence
starts, and
when trace
ends.
Sequence
Abort Com-
pletion Flag
Board:
CIO 190910 (port 1)
CIO 191910 (port 2)
Unit:
n + 9 bit 10 (port 1)
n + 19 bit 10 (port 2)
This flag is turned ON when a sequence is
ended for the next process or for an error
processing with an ABORT command.
1: Sequence aborted
0: Sequence not aborted
Startup
(see note)
When
sequence
aborts
When
sequence
starts
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...