Setup Area Allocations
Section 4-2
4-2-2
Setup Area Contents
m = 100
×
Unit No.
Port Settings
The setting for the port settings determine if the default settings or user set-
tings will be used for port 1 and port 2. Be sure to use the same settings as
the RS-232C port on the host computer connected via the Host Link System.
If the default port settings are specified, then the setting of bits 00 to 04 and
the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 9,600 bps, start bits:
1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits.
If user port settings are specified, set bits 00 to 04 and set the baud rate in
D32001.
Setting Example:
0100 Hex = Host link mode with default port settings.
Serial Communications
Mode
Set the serial communications mode to 5 Hex to use Host Link communica-
tions. The default setting of 0 Hex can also be used to operate in Host Link
mode with unit number 00.
Words
Bit
Setting contents
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1
Port 2
Port 1
Port 2
D32000
D32010
m
m + 10
15
Port settings
0: Defaults; 1: User settings
12 to 14 Reserved
08 to 11 Serial communications mode
0: Default (Host Link)
5: Host Link
05 to 07 Reserved
04
Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
03
Data length
0: 7 bits; 1: 8 bits
02
Stop bits
0: 2 bits; 1: 1 bit
01
Parity
0: Yes; 1: No
00
Parity
0: Even; 1: Odd
D32001
D32011
m + 1
m + 11
04 to 15
Reserved
00 to 03 Baud rate (bps)
0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600; 7: 19,200;
8: 38,400; 9: 57,600; A: 115,200
D32002
D32012
m+ 2
m + 12
15
Send delay time 0: Default (0 ms); 1: Setting in bits 00 to 14
00 to 14 Send delay (0000 to 7530 hex) (Unit: 10 ms)
D32003
D32013
m + 3
m + 13
15
CTS control
0: No; 1:Yes
14
1:N/1:1 protocol setting (Unit Ver. 1.2 or later only)
1: 1:1 protocol; 0: 1:N protocol
If the Host Link compatible device mode is set between 0 and 2 hex
(mode A or B), the setting in this bit is invalid (always 1:N Host
Links)
11 to 13
Reserved
08 to 10
Host Link compatible device mode
0 hex: Default (mode A)
1 hex: Mode A (CS/CJ/C)
2 hex: Mode B (CVM1/CV)
3 hex: Mode C (C200H)
4 hex: Mode D (C500/120)
00 to 07
Host Link unit number (00 to 1F hex)
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...