74
PROFIBUS-DP Master DTM
Section 3-3
Global_Control Messages
Global_Control messages can be initiated by the user from the Online Opera-
tions tab. The user can select the Global_Control commands.
• Freeze.
• Unfreeze.
• Sync.
• UnSync.
All commands can be transmitted independent from each other, i.e. all can be
send at the same time. However, their effects are not independent, as for
example sending Freeze and Unfreeze at the same time results in an
Unfreeze command at the slaves.
Selecting the Groups
Specific groups to send the Global_Control command to can be selected, by
selecting the appropriate checkboxes. Selecting the All Slaves checkbox can
select all slaves, and it will disable the individual check boxes.
Transmit Global_Control
command
In order to transmit the Global_Control, press the Transmit button. The com-
mand will be transmitted only once. Both the Global_Control command con-
tents, group select and the transmit command are transferred to the Unit
though its CIO words (see section
4-2-1 Software Switches 1 (Word n)
and
section
4-2-2 Global_Control Message (Word n+2)
!Caution
When transmitting a Global_Control command, it may interfere with attempts
from the PLC Program to write to the same software switches. Care should be
taken to avoid these situations.
3-3-3
Connecting to the PROFIBUS-DP Master Unit
Configuring
communication
The PROFIBUS-DP Master DTM uses CX-Server to connect to the Unit for
both downloading a configuration as well as monitoring the master Unit. In
order to setup the communication to the Unit, perform the following proce-
dure.
1,2,3...
1.
Open the Master DTM Configuration Interface, Device Setup tab (see sec-
tion
3-3-1 Configuration User Interface
).
2.
Select the Unit Number. It must match the unit number set on the PROFI-
BUS-DP Master Unit, through the rotary switch on the front.
3.
Select the Configure button to start CX-Server.
CX-Server
Up on pressing the Configure button, CX-Server is launched and displays the
CX-Server User Interface as shown below.
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...