128
Overview
Section 7-1
7-1
Overview
The PROFIBUS-DP Master Unit and the Configuration software package pro-
vides extensive means for troubleshooting, which can be used to quickly
determine errors in the Unit, in the configuration, in the network, and/or in
remote slave stations, allocated to the PROFIBUS-DP Master unit.
Troubleshooting on the
Master Unit
For troubleshooting purposes, the following error indicators can be used:
• LED indicators on the front of the Unit
Three red error LED indicators and four status LED indicators show Unit
and network status and errors.
• CIO Words
Unit Status (CIO Word n + 4) containing status and error flags of the Unit,
and Master Status 2 (CIO Word n+6) containing error information about
the PROFIBUS network and the PROFIBUS functions of the Unit.
• The Error Log collects error codes for various error events. Serious errors
are stored in non-volatile memory and can be retrieved, even after a Unit
power down.
• FINS command provide defined response codes, which can indicate spe-
cific errors.
Note n = CIO 1500 + (25 x unit number).
This section provides a number of procedures for troubleshooting, based on
the error indicators listed above.
Troubleshooting the
Configuration Software
The Configuration software, i.e. CX-Profibus, the PROFIBUS-DP Master DTM
and the Generic Slave DTM provide several mechanisms for error detection
and correction:
• Errors occurring in CX-Profibus are displayed in pop-up message win-
dows and/or the error log window. The contents of the error log window
can be copied to the clipboard to allow analysis afterwards.
• CX-Profibus provides a FDT communication log window, which can be
copied to the clipboard. Analysis of this communication may provide addi-
tional information in case errors occur.
Troubleshooting the
network
The PROFIBUS-DP Master DTM and the Generic Slave DTM diagnostics
information windows, which can display:
• Indications of errors in the PROFIBUS interface of the Unit
• Indications of errors in the communication between the PROFIBUS-DP
Master unit and remote slave stations.
• Indications of errors in the remote slave stations, allocated to the PROFI-
BUS-DP Master unit.
The CX-Profibus and DTM capabilities for troubleshooting are extensively dis-
cussed in
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...