Section 2
Description of All Components
14
2-3
Expansion I/O Backplane
The Expansion I/O Backplane shown in the following diagram, can be used
to expand the C500 PC. An Expansion I/O Rack is just like a CPU Rack, ex-
cept a CPU is not mounted. However, a Power Supply is needed for each
Expansion I/O Rack. There are three models of Expansion I/O Backplane
available.
Expansion I/O Backplane
I/O Interface Unit
An I/O Interface Unit must be mounted to an Ex-
pansion I/O Rack in order to connect the Expan-
sion I/O Rack to another Expansion I/O Rack.
I/O Units
Expansion I/O Power Supply
2-4
I/O Power Supply
Just as a Power Supply must be mounted to the CPU Rack, a Power Supply
must also be mounted to each Expansion I/O Backplane. There are two
Power Supplies available; 100 to 120/200 to 240 VAC and 24 VDC, both of
which are explained below. For details, refer to
Appendix B Specifications.
Model
Supply Voltage
Output
Capacity
Available
Current for I/O
Units
240 VDC
Output
Terminal
3G2A5-PS222-E
100 to 120/200
to 240 VAC
(selectable)
7A 5 VDC
6.5 A
Provided
3G2A5-PS212-E
24 VDC
7 A 5 VDC
6.5 A
Not provided
Note
Be sure to keep the total power consumed by all the Units mounted
on a Rack within the value stated in the table above. For example, do
not mount I/O Units with a total current consumption of 7A to a Rack
supplied by a 7 A Power Supply. As shown in the table above, the
available current for I/O Units is only 6.5 A. For details concerning
current consumption, refer to
Summary of Contents for SYSMAC C500
Page 1: ...Cat No W132 E1 4 Programmable Controller SYSMAC C500...
Page 2: ...C500 Programmable Controller Installation Guide Revised May 2000...
Page 37: ...29 SECTION 4 System Connections 4 1 Current Consumption 30 4 2 I O Connections 33...
Page 49: ...43 SECTION 6 Power Considerations...
Page 54: ...49 SECTION 7 Safety Considerations...
Page 58: ...53 A Inspection and Maintenance 54 B Specifications 57 C Standard Models 97 Appendix...
Page 96: ...Appendix B Specifications 91 A shape I O Unit B shape I O Unit...
Page 97: ...Specifications Appendix B 92 C shape I O Unit D shape I O Unit...