4-44
4-2 Function Mode
4
Func
tions
Jogging Frequency
• The Inverter may easily lead to a trip if the jogging frequency is set to high. Adjust A038 so that the
Inverter does not trip.
Jogging Stop Selection
• The deceleration time depends on the currently selected deceleration time in F003, F203, A093,
or A293. When switching to normal operation, turn off the JG terminal after the deceleration time
elapses, and enter the RUN command again.
Note1: To perform the jogging operation, turn on the JG terminal before the FW or RV terminals.
(Do the same if the RUN command source is set to the Digital Operator.)
Note 2: If A039 is set to 02, data setting for the DC injection braking is required.
2nd Control Function and Special 2nd Function
• This function is used to operate by switching two different types of motors.
• By allocating 08 (SET) or 53 (SP-SET) to the desired multi-function input and then turning on/off
the SET or SP-SET terminal, you can switch and control two different motors.
• Switch to the 2nd control function at the SET terminal after turning off the RUN command and the
Inverter output.
• You can switch to the 2nd control function at the SP-SET terminal during operation.
JG
FW
RV
Output frequency
A038
(When A039 = 01)
JG
FW
Output frequency
Jogging does not function if the FW
signal is turned on first.
Data
Symbol
Function name
Status
Description
08
SET
2nd control
ON
Enables the parameter for the 2nd motor.
OFF
Disables the parameter for the 2nd motor.
53
SP-SET
Special 2nd function
ON
Enables the parameter for the special 2nd motor.
OFF
Disables the parameter for the special 2nd motor.
Available input terminals
C001, C002, C003, C004, C005
Summary of Contents for SYSDRIVE 3G3MX-A2002
Page 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Page 90: ......
Page 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Page 180: ......
Page 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Page 188: ......
Page 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Page 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Page 230: ......
Page 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Page 249: ...INDEX...