250
GRT1-CT1(-1) Counter Units
Section 7-4
■
Default Settings
Press the
Default Setting
Button on the
Preset
Tab Page to set the following
default value.
Range 0 Tab Page
The tab page to set a comparison range is displayed only when the range is
enabled. Click the
Range 0
Button on the
Counter
Tab Page to enable using
the range and display the
Range 0
Tab Page. The digital output will not be
controlled by the comparison function unless a range is set.
Note
The digital output will be controlled by the Range only when the Output Con-
trol Bits (bits 12 and 13 of word n+2) are OFF.
The Range 0 Tab Page is used to set a comparison range for the counter
value. The range has a lower limit (LL) and an upper limit (UL). The digital out-
put can be controlled according to the counter value in respect to this range.
Click the
Range 0
Tab in the Edit Unit Parameters Window. The
Range 0
Tab
Page will be displayed.
■
Operation
The output will be controlled according to the relationship between the
counter value and the range settings as follows:
• If UL > LL, the digital output will be ON when LL
≤
Counter value
≤
UL,
and will be OFF otherwise.
• If UL < LL, the digital output will be OFF when UL
≤
Counter value
≤
LL,
and will be ON otherwise.
• If UL = LL, the digital output will be ON when LL = Counter value = UL,
and will be OFF otherwise.
The following figures illustrate the first two cases.
Setting
Default value
Preset value
0
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......