209
Temperature Input Units
Section 6-4
5. Click the
Download
Button, and then click the
Reset
Button to reset the
Unit.
6. Click the
OK
Button to exit.
■
Setting the Last Maintenance Date of the Connected Device
1,2,3...
1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select
Pa-
rameters - Edit
. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3. Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit
Parameters Window will be displayed.
4. Click the tab page for the input that is connected to a connecting device
requiring the last maintenance date to be set. Select the applicable date
from the pull-down menu in the
Last Maintenance Date
Field. (To enter the
current date, select
Today
, which is at the bottom of the pull-down menu.)
5. Return to the
General
Tab Page, click the
Download
Button, and then
click the
Reset
Button to reset the Unit.
6. Click the
OK
Button to exit.
Temperature
Cumulative Counter
(Cumulated Count)
The cumulative counter calculates an approximation of the integral of the tem-
perature input value over time to calculate the heat exposure to sensors or
equipment. Either hours (
°
C (
°
F)
×
hours) or minutes (
°
C (
°
F)
×
minutes) can
be selected. For example, a cumulated count of “100.0” indicates a value
equivalent to a temperature input value of 100
°
C (
°
F) for one hour, if hours
has been selected as the unit.
The cumulated count is stored in a 4-byte (2-word) area according to the set
unit for 300 divisions (See notes 1 and 2.).
A threshold value can be set to monitor the cumulated count. If the cumulated
count exceeds the threshold value, the Cumulative Counter Flag in the Warn-
ing Status Area will turn ON and the
Threshold Cumulated Counter Over
Sta-
tus Check Box in the Maintenance Window will be selected.
Note
(1) If
°
F is selected, the integration will be performed on the
°
F values.
(2) If the 1/100 Display Mode is selected, integration will be performed on the
100 times the binary data.
Summary of Contents for SMARTSLICE GRT1-DRT
Page 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Page 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 20: ...xx EC Directives 6 ...
Page 62: ...42 Connecting Turnback Cables Section 3 3 ...
Page 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 322: ...302 Troubleshooting by Unit Section 9 5 ...
Page 350: ...330 Explicit Messages Appendix A ...
Page 354: ...334 Power Consumption and Weight Tables Appendix C ...
Page 356: ...336 I O Current Consumption Table Appendix D ...
Page 364: ...344 Revision History ...
Page 365: ......