background image

1

Switch Mode Power Supply

S8VS 

(15/30/60/90/120/180/240/480-W Models)

Indication Monitor for 
Visualization of Operating Status
For Even Greater Maintenance 
Efficiency 

*

• Status displayed on 3-digit, 7-segment display. 

*

• Signal output notifications at 90 W or more. 

*

• Conformity to various safety standards for global 

usability.

• Varied coverage with 3-year warranty.
• DIN rail mounting supported.

*

Models with indication monitor

Model Number Structure

Model Number Legend

Note: Not all combinations are possible. Refer to 

List of Models

 in 

Ordering Information

, below.

Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.

For the most recent information on models that have been certified for 

safety standards, refer to your OMRON website.

!

Refer to 

Safety Precautions for All Power Supplies

 and 

Safety 

Precautions

 on page 32.

Recommended Noise Filter

Noise filter
S8V-NF

For more information, refer to 

S8V-NF Noise 

Filter Data Sheet

 (Cat. No. T212-E1).

1

2

3 4 5 6

S

8

VS- 

@@@@@@@@

-

@

1. Power Ratings

015: 15 W
030: 30 W
060: 60 W
090: 90 W
120: 120 W
180: 180 W
240: 240 W
480: 480 W

2. Output voltage

(VDC)

05: 5 V
12: 12 V
24:  24 V

3. Indication monitor

None: Without indication monitor (standard model)
A: 

With indication monitor (maintenance forecast 
monitor)

B: 

With indication monitor (total run time monitor)

BE:

With indication monitor but without alarm output 
(total run time monitor)

4. Alarm output

None: Sinking (Emitter COM) 

*

P:

Sourcing (Collector COM)

Note: No alarm output possible with 60-W models.

*

Both sinking and sourcing outputs are available for 

480-W models.

5. UL Class 2 Output Standards (UL 1310) 

None: Does not conform. 

*

S:

Conforms.

*

15-W, 30-W, and 60-W models conform to Class 2 

output standards (UL 1310).

Note: The S option is available only for 90-W models.

6. Terminal Block Form

None: Screw terminal block
F:

Screwless terminal block

Summary of Contents for S8VS

Page 1: ...autions for All Power Supplies and Safety Precautions on page 32 Recommended Noise Filter Noise filter S8V NF For more information refer to S8V NF Noise Filter Data Sheet Cat No T212 E1 1 2 3 4 5 6 S8...

Page 2: ...240 VAC 20 A Peak current 30 A 200 VAC S8VS 48024 S8VS 48024 F Power ratings Input voltage Output voltage VDC Output current Alarm output 2 UL Class 2 Output standards Model number screw terminal bloc...

Page 3: ...500 ms typical 560 ms typical 560 ms typical With 200 VAC input 340 ms typical 360 ms typical 400 ms typical 360 ms typical 380 ms typical 400 ms typical Output hold time at rated I O 2 With 100 VAC i...

Page 4: ...ms typical With 200 VAC input 400 ms typical 290 ms typical Output hold time at rated I O 2 With 100 VAC input 34 ms typical 33 ms typical With 200 VAC input 158 ms typical 154 ms typical Additional...

Page 5: ...l With 200 VAC input 132 ms typical 136 ms typical Additional functions Overload protection 2 105 to 160 of rated load current 101 to 110 of rated load current for the S8VS 09024 S inverted L voltage...

Page 6: ...ut 30 VDC max 50 mA max 9 No No Yes transistor output 30 VDC max 50 mA max 9 No Total run time monitor indication 5 No Yes selectable No Yes selectable Total run time monitor output 5 No Yes transisto...

Page 7: ...ut 30 VDC max 50 mA max 9 No Yes transistor output 30 VDC max 50 mA max 9 Undervoltage alarm indication 5 No Yes selectable No Yes selectable Undervoltage alarm output terminals No Yes transistor outp...

Page 8: ...ircuit Noise filter Inrush current protection Rectifier Smoothing circuit Overcurrent detection circuit S8VS 015 15 W Voltage detection circuit Photocoupler Rectifier smoothing circuit AC L INPUT AC N...

Page 9: ...thmetic operation circuit Display circuit Switch Overvoltage detection circuit Inrush current protection circuit Rectifier S8VS 06024A 60 W S8VS 06024B 60 W S8VS 06024 60 W AC L INPUT AC N V V DC OUTP...

Page 10: ...rent protection circuit Drive control circuit Arithmetic operation circuit Alarm DC Low Voltage detection circuit Overcurrent circuit Overvoltage detection circuit Current detection circuit S8VS 09024...

Page 11: ...rrent circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Arithmetic operation circuit Rectifier smoothing circuit V V DC OUTPUT Alarm DC Low S8VS 12024A 120 W...

Page 12: ...detection circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit V V DC OUTPUT Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low S8VS 18024A 18...

Page 13: ...control circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low V V V V DC OUTPUT S8VS 24024A...

Page 14: ...circuit Current detection circuit V V V V DC OUTPUT V V S8VS 48024A S8VS 48024B Display circuit Switch Arithmetic operation circuit S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 90 120 180 and...

Page 15: ...ety standards Always ground this terminal No Name Function 1 Input terminals L N Connect the input lines to these terminals 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2...

Page 16: ...als 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2 3 DC Output terminals V V Connect the load lines to these terminals 4 Output indicator DC ON Green Lights while a direct...

Page 17: ...ent Apk Lights up during indication of peak hold current Yrs Lights up during indication of maintenance forecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Ligh...

Page 18: ...acket is used Note 1 Internal parts may occasionally deteriorate or be damaged Do not use the Power Supply in areas outside the derating curve i e the area shown by shading A in the above graph 2 If t...

Page 19: ...uent inrush current or overloading at the load end Do not use the Power Supply for such applications Peak Output Current S8VS 48024 only The boost current is a temporary current that exceeds the rated...

Page 20: ...S 06024A S8VS 06024B Further an output undervoltage output terminal DC LOW to an external device is given from the transistor to notify of the error excluding S8VS 06024A S8VS 06024B S8VS 24BE Output...

Page 21: ...ng 15 max Five M4 Square Washer Screw Rail Stopper 35 4 74 95 1 40 1 S8VS 06024 60 W S8VS 06024A 60 W S8VS 06024B 60 W 1 7 10 110 3 11 max 116 2 Five M4 Square Washer Screw 4 5 Sliding 15 max Screw Le...

Page 22: ...VS 24024BE 240 W S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 150 1 7 70 10 1 Rail Stopper Rail Stopper Screw Lessly Terminal The 2 5 mm pace 122 2 127 2 1 Nine M4 Square Washer Screw 4 5 Slid...

Page 23: ...15 max 115 1 10 S8VS 18024 F 180 W S8VS 18024A F 180 W S8VS 18024B F 180 W S8VS 18024BE F 180 W 1 50 10 100 1 10 117 6 7 max 119 3 Rail Stopper Rail Stopper 97 3 35 4 4 5 Sliding 15 max 115 1 S8VS 24...

Page 24: ...over Order Separately Note Terminal block cover attaches to the body Please order from the loss time 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the...

Page 25: ...unting Bracket For 60 90 120 W models S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W...

Page 26: ...no key operation for 30 seconds or more Model indication Setting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and dis...

Page 27: ...r at the same time When undervoltage alarm is indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication No...

Page 28: ...method Setting after restoration Noise detected in voltage or current No change Automatic reset No change h t Overheated Maintenance forecast output terminal Yrs turns OFF Automatic reset No change e0...

Page 29: ...g time are indicated alternately If the setting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes l...

Page 30: ...rchase even if indication and output of maintenance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indica...

Page 31: ...larm set value reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode The S8VS 09024BE S8VS 12024BE S8VS 18024BE and S8VS 24024BE...

Page 32: ...max on the left and right 60 W 90 W 120 W 180 W 240 W and 480 W Models Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts U...

Page 33: ...n Monitor Except 60 W Models It may take from several years to more than 10 years under general operating conditions for the power supply to output the maintenance forecast monitor alarm S8VS 24A The...

Page 34: ...circuited a reverse voltage will be generated inside the Power Supply If this occurs the Power Supply may possibly deteriorate or be damaged Always connect a diode as shown in the figure Select a dio...

Page 35: ...t voltage x rated output current In Case There Is No Output Voltage The possible cause for no output voltage may be that the overcurrent or overvoltage protection has operated The internal protection...

Page 36: ...MEMO 36...

Page 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 38: ...Estates IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www i...

Reviews: