11 Adjustment Functions
11 - 18
G5-series Linear Motors/Servo Drives With Built-in EtherCAT Communications
*1
If the damping control function is not used, set the damping frequency to a value between 0 and 0.9 Hz.
*2
This object is also disabled when the damping frequency is disabled. In addition, the upper limit of the set
value is restricted to the corresponding damping frequency or the value of (2000 minus damping frequency),
whichever is the smaller.
Precautions for Correct Use
Precautions for Correct Use
•
The damping frequency and damping filter settings are switched when the position command
value per 0.250 ms changes from 0 to a value other than 0 while the positioning completed
output is ON.
In particular, if the damping frequency is changed to a larger value or disabled and a large
Position window is set, the motor may move suddenly immediately after switching.
This occurs due to the pulses accumulated in the filter at the time of switching, which are
distributed rapidly after switching to restore the normal position.
Be careful as the motor may temporarily operate faster than the expected command speed.
•
There is a delay from the time when the damping frequency and damping filter settings are
changed until the new values are applied in internal calculations. If the filter switch wait time
expires during this delay, the change may be placed on hold.
11-5-2 Objects Requiring Settings
Index
Name
Description
Reference
3213 hex
Damping Filter
Selection
Select the Damping Filter Switching Mode according to the
condition of the unit.
0:Up to two filters can be used simultaneously.
3:Switching with command direction
3214 hex
Damping
Frequency 1
Set damping frequency 1 to suppress vibration at the end of the
load in damping control.
Measure the frequency of vibration at the tip of the load and make
the setting in units of 0.1 Hz.
The effective frequency setting range is 1.0 to 200.0 Hz.
*1
3215 hex
Damping Filter 1
Setting
When Damping Frequency 1 (3214 hex) is set,
*2
reduce this
setting if force saturation occurs or increase this setting to
increase operation speed.
They are normally set to 0.
3216 hex
Damping
Frequency 2
Set damping frequency 2 to suppress vibration at the end of the
load in damping control.
The function the same with the Damping Frequency 1 (3214 hex).
3217 hex
Damping Filter 2
Setting
The function the same with the Damping Filter 1 Setting
(3215 hex).
3218 hex
Damping
Frequency 3
Set damping frequency 3 to suppress vibration at the end of the
load in damping control.
The function the same with the Damping Frequency 1 (3214 hex).
3219 hex
Damping Filter 3
Setting
The function the same with the Damping Filter 1 Setting
(3215 hex).
3220 hex
Damping
Frequency 4
Set damping frequency 4 to suppress vibration at the end of the
load in damping control.
The function the same with the Damping Frequency 1 (3214 hex).
3221 hex
Damping Filter 4
Setting
The function the same with the Damping Filter 1 Setting
(3215 hex).