12 Troubleshooting and Maintenance
12-2
G5 Series AC Servo Drives With Built-in EtherCAT Communications, Linear Motor Type
12-1 Actions for Problems
The following sections describe the preliminary checks and precautions that will be required if a
problem occurs.
This section explains the preliminary checks and analytical software required to determine the cause of
a problem if one occurs.
•
Check the voltage at the power supply input terminals.
Main Circuit Power Supply Input Terminals (L1, L2, L3)
Control Circuit Power Supply Input Terminals (L1C, L2C)
If the voltage is out of range, there is a risk of operation failure. Be sure that the power supply is
within the specified range.
•
Check the voltage of the sequence input power supply (+24 VIN terminal (CN1 pin 7)).
It must be between 11 and 25 VDC.
If the voltage is out of range, there is a risk of operation failure. Be sure that the power supply is within
the specified range.
Make an analysis using the 7-segment display on the front of the Servo Drive or using CX-Drive tools.
When an Error Has Occurred
Check the error display (
) and make an analysis based on the error that is indicated.
When an Error Has Not Occurred
Make an analysis according to the error conditions.
on page 12-11 for details.
12-1-1 Preliminary Checks When a Problem Occurs
Checking the Power Supply Voltage
Model
Capacity
Power supply voltage
R88D-KN
L-ECT-L
100 W to 400 W
Single-phase 100 to 120 VAC (85 to 132 V) 50/60 Hz
R88D-KN
H-ECT-L
100 W to 1.5 kW
Single-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
750 W to 1.5 kW
3-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
2 kW to 15 kW
3-phase 200 to 230 VAC (170 to 253 V) 50/60 Hz
R88D-KN
F-ECT-L
750 W to 15 kW
3-phase 380 to 480 VAC (323 to 528 V) 50/60 Hz
Model
Capacity
Power supply voltage
R88D-KN
L-ECT-L
100 W to 400 W
Single-phase 100 to 120 VAC (85 to 132 V) 50/60 Hz
R88D-KN
H-ECT-L
100 W to 1.5 kW
Single-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
2 kW to 15 kW
3-phase 200 to 230 VAC (170 to 253 V) 50/60 Hz
R88D-KN
F-ECT-L
750 W to 15 kW
24 VDC (21.6 to 26.4 V)
Checking Whether an Error Has Occurred