396
SIEPCYEUOQ2V01A Q2V Technical Manual
◆
U3: FAULT HISTORY
No.
(Hex.)
Name
Description
MFAO Signal Level
U3-01 to U3-04
(0090 - 0093)
(0800 - 0803)
1st to 4th Newest Fault
Shows the fault history of the first to fourth most recent faults.
Note:
The drive saves the
U3-01 to U3-04 [1st to 4th Newest Fault]
fault histories to two types of
registers at the same time for the Modbus communications.
No signal output available
U3-05 to U3-10
(0804 - 0809)
5th to 10th Newest Fault
Shows the fault history of the fifth to tenth most recent faults.
No signal output available
U3-11 to U3-14
(0094 - 0097)
(080A - 080D)
1st to 4th NewstFlt Timing
Shows the cumulative operation time when the first to fourth most recent faults occurred.
Unit: 1 h
Note:
The drive saves the
U3-11 to U3-14 [1st to 4th NewstFlt Timing]
the cumulative operation
time to two types of registers at the same time for the Modbus communications.
No signal output available
U3-15 to U3-20
(080E - 0813)
1st to 10th NewstFlt Timing
Shows the cumulative operation time when the fifth to tenth most recent faults occurred.
Unit: 1 h
No signal output available
◆
U4: MAINTENANCE
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-01
(004C)
Cumulative OpeTime
Shows the cumulative operation time of the drive.
Use parameter
o4-01 [Cum.Oper TimeSetting]
to reset this monitor. Use parameter
o4-02 [Cum.
Oper TimeSelect]
to select the cumulative operation times from:
•
The time from when the drive is energized until it is de-energized.
•
The time at which the Run command is turned ON.
The maximum value that the monitor will show is
99999
. After this value is more than
99999
, the
drive automatically resets it and starts to count from
0
again.
Unit: 1 h
Note:
The Modbus communication data is shown in 10 h units. Use register 0099H for data in 1 h
units.
10 V: 99999 h
U4-02
(0075)
Num of Run Commands
Shows how many times that the drive has received a Run command.
Use parameter
o4-13 [NumOfRunCom Init Counter]
to reset this monitor. The maximum value
that the monitor will show is
65535
. After this value is more than
65535
, the drive automatically
resets it and starts to count from
0
again.
Unit: 1
10 V: 65535 times
U4-03
(0067)
Fan Oper.Time
Shows the cumulative operation time of the cooling fans.
Use parameter
o4-03 [Fan.Oper Setting]
to reset this monitor. The maximum value that the
monitor will show is
99999
. After this value is more than
99999
, the drive automatically resets it
and starts to count from
0
again.
Unit: 1 h
Note:
The Modbus communication data is shown in 10 h units. Use register 009BH for data in 1 h
units.
10 V: 99999 h
U4-04
(007E)
Cool Fan Maintenance
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter
o4-03 [Fan.Oper Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
10 V: 100%
U4-05
(007C)
Capacitor Maintenance
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the replacement life of the electrolytic capacitors.
Use parameter
o4-05 [Cap.Maint.Setting]
to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
10 V: 100%
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...