4-4 Regenerative Energy Absorption
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
4
System Design
Connecting an External Regeneration Resistor
R88D-KNA5L-ML2/-KN01L-ML2/-KN02L-ML2/-KN01H-ML2/-KN02H-ML2/-KN04H-ML2
Normally B2 and B3 are open.
If an External Regeneration Resistor is necessary, connect the External Regeneration Resistor
between B1 and B2 as shown in the diagram below.
Precautions for Correct Use
Connect the thermal switch output so that the main circuit power supply is shut OFF when the
contacts open.
When using multiple External Regeneration Resistors, connect each thermal switch in series.
The resistor may be damaged by burning, or cause fire if it is used without setting up a power
supply shutoff sequence using the output from the thermal switch.
R88D-KN04L-ML2/-KN08H-ML2/-KN10H-ML2/-KN15H-ML2/-KN20H-ML2/-KN30H-ML2/
-KN50H-ML2/-KN06F-ML2/-KN10F-ML2/-KN15F-ML2/-KN20F-ML2/-KN30F-ML2/-KN50F-ML2
Normally B2 and B3 are short-circuited.
If an External Regeneration Resistor is necessary, remove the short-circuit bar between B2
and B3, and then connect the External Regeneration Resistor between B1 and B2 as shown
in the diagram below.
Precautions for Correct Use
Connect the thermal switch output so that the main circuit power supply is shut OFF when the
contacts open.
When using multiple External Regeneration Resistors, connect each thermal switch in series.
The resistor may be damaged by burning, or cause fire if it is used without setting up a power
supply shutoff sequence using the output from the thermal switch.
Servo Drive
B1
B3
External Regeneration Resistor
θ >
Thermal switch output
B2
Servo Drive
B1
B3
External Regeneration Resistor
Remove the short-circuit bar between B2 and B3.
θ >
Thermal switch output
B2