4 - 31
4 Installation and Wiring
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
4
-4 Wiring
E
x
amp
les
4
4-
4-2 Wiring the Analog Output Un
its
Precautions for Correct Use
To ensure this NX Unit is kept in the best operating condition, observe the following points
when wiring to avoid the effects of the noise.
• Use a shield wire (2 conductors, twisted wire) or a shield wire (3 conductors) as the input
connection line for each output. Connect the shield according to the specifications of the
input device.
• Wire the output connection lines and power lines (e.g., AC power supply lines or power
lines) separately. Do not place such lines in the same duct.
• Insert a noise filter into the power supply input section if noise comes from power supply
lines when using the same power supply to power an electrical welder or an electric dis-
charge machine, or there is a high-frequency source nearby.
4-4-2
Wiring the Analog Output Units
Voltage
Voltage output
−
IOV
IOG
IOV
IOG
IOV
IOG
IOV
IOG
V1+
IOG
IOV
IOV
A1
B1
A8
B8
IOG
V2+
IOG
IOV
IOV
IOG
24 VDC
A1
B1
A8
B8
V3+
V4+
Additional I/O
Power Supply Unit
NX-PF0630
Voltage Output Unit
NX-DA3603
Summary of Contents for NX-AD series
Page 289: ......