76
DST1 Series Monitoring
Section 4-7
Instance ID: 333
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
Instance ID: 342
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
4-7-4
Monitoring the DST1-XD0808SL-1
Note
(1) Overall Status
Read Data Format (Read Size: 1 Byte)
Status
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1
Safety out-
put termi-
nal No. 3
monitor
Safety out-
put termi-
nal No. 2
monitor
Safety out-
put termi-
nal No. 1
monitor
Safety out-
put termi-
nal No. 0
monitor
Safety out-
put termi-
nal No. 3
status
Safety out-
put termi-
nal No. 2
status
Safety out-
put termi-
nal No. 1
status
Safety out-
put termi-
nal No. 0
status
+2
Muting
lamp status
Reserved
Test output
terminal No.
3 status
Test output
terminal No.
2 status
Test output
terminal No.
1 status
Test output
terminal No.
0 status
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Test output
terminal No.
3 status
Test output
terminal No.
2 status
Test output
terminal No.
1 status
Test output
terminal No.
0 status
Safety out-
put termi-
nal No. 3
monitor
Safety out-
put termi-
nal No. 2
monitor
Safety out-
put termi-
nal No. 1
monitor
Safety out-
put termi-
nal No. 0
monitor
Service code
Class ID
Instance ID
Request data
(attribute ID)
Safety input monitor
Safety input status
Safety output monitor
Safety output status
Overall status (See note 1.)
Input value/
status
0E hex
04 hex
Refer to the table in
note 4.
03 hex
Safety input error cause
(See note 2.)
Error cause
0E hex
3D hex
01 to 08 hex
6E hex
Safety output error cause
(See note 3.)
Error cause
0E hex
3B hex
01 to 08 hex
6E hex
+0
Status
Bit
Meaning
0
Input Power Supply Voltage Monitor Flag
0: I/O power supply ON, ON: I/O power supply OFF
1
Output Power Supply Voltage Monitor Flag
OFF: I/O power supply ON, ON: I/O power supply OFF
2
Network Power Supply Voltage Monitor Error Flag
0: Normal (higher than monitor set value), ON: Error (not higher than
monitor set value)
3
Module Maintenance Flag
OFF: Within range (lower than monitor set value), ON: Out of range
(not lower than monitor set value)
4
Operation Mode Flag
OFF: Other than RUN, ON: RUN
Summary of Contents for NE1A-EDR01
Page 1: ...OPERATION MANUAL Cat No Z912 E1 01 NE1A Series NE1A EDR01 EtherNet IP DeviceNet Router...
Page 2: ...NE1A Series EtherNet IP DeviceNet Router NE1A EDR01 Operation Manual Produced July 2007...
Page 3: ...iv...
Page 7: ...viii TABLE OF CONTENTS...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...24 ED Router Settings Section 2 5...
Page 53: ...36 Error History Section 3 3...
Page 97: ...80 DST1 Series Monitoring Section 4 7...
Page 101: ...84 Settings from the Network Configurator Appendix B...
Page 105: ...88 Glossary...
Page 107: ...90 Revision History...