17
Connecting to DeviceNet
Section 2-3
2-3-3
DeviceNet Node Address and Baud Rate Software Settings
Use the following procedure to set the ED Router DeviceNet node address
and baud rate from the Network Configurator.
1,2,3...
1.
Select
Programs - OMRON Network Configurator for DeviceNet Safety
- Network Configurator
from the Start Menu. The Network Configurator
will be started.
2.
Connect the Network Configurator online. (First set the interface with
Op-
tion - Select Interface
, and then select
Network - Connect
.)
3.
Select DeviceNet in the Network Configuration Window. (For example,
click the
DeviceNet_1
Tab.)
4.
Select
Tool - Node Address/Baud Rate Setting
.
The following dialog box will be displayed.
5.
Specify the present node address of the target ED Router in the
Target
Node Address
Field.
6.
To change the node address, specify a new node address in the
New Node
Address
Field and click the
Change
Button.
The node address of the ED Router will be changed.
7.
To change the baud rate, select the rate in the
New Baud Rate
Field and
click the
Change
Button.
The baud rate of the ED Router will be changed.
Summary of Contents for NE1A-EDR01
Page 1: ...OPERATION MANUAL Cat No Z912 E1 01 NE1A Series NE1A EDR01 EtherNet IP DeviceNet Router...
Page 2: ...NE1A Series EtherNet IP DeviceNet Router NE1A EDR01 Operation Manual Produced July 2007...
Page 3: ...iv...
Page 7: ...viii TABLE OF CONTENTS...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...24 ED Router Settings Section 2 5...
Page 53: ...36 Error History Section 3 3...
Page 97: ...80 DST1 Series Monitoring Section 4 7...
Page 101: ...84 Settings from the Network Configurator Appendix B...
Page 105: ...88 Glossary...
Page 107: ...90 Revision History...