A - 13
Appendices
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
A
-3 T
ag D
at
a
L
in
k
C
o
nn
ec
ti
o
n Se
tti
ng
Pro
c
ed
ur
es
A
A-3-
1 Preface
A-3 Tag Data Link Connection Setting
Procedures
The internal data (parameters) of the tag data link supported by the Main Unit is assigned to any
one of the four tag sets. Therefore, it is necessary to select the tag set to use according to the pur-
pose of the customer, and then set it. See below for the size and contents of the four tag sets.
Size and Contents of Tag Sets
You can set tag data link settings using the Network Configurator for EtherNet/IP.
When using the CS/CJ-series PLC as an originator, use the Network Configurator for EtherNet/IP
supporting the model and version of the CPU Unit. Refer to the CS/CJ Series EtherNet/IP Units
Operation Manual (Cat. No. W465) for the setting status of the setting tool.
The setting method when the CS/CJ-series PLC is an originator is as follows.
A-3-1
Preface
Identification number
(Instance ID of
Assembly object)
Size
Function
64 hex
(Input_100)
128 bytes
• K6PM-TH status
• Running Time data
• Status of sensors 1 to 31
• Alarm status of sensors 1 to 31
65 hex
(Input_101)
380 bytes
• Status of sensors 1 to 10
• Alarm status of sensors 1 to 10
• Internal temperature value of sensors 1 to 10
• Segment current temperature value of sensors 1 to 10
66 hex
(Input_102)
380 bytes
• Status of sensors 11 to 20
• Alarm status of sensors 11 to 20
• Internal temperature value of sensors 11 to 20
• Segment current temperature value of sensors 11 to 20
67 hex
(Input_103)
418 bytes
• Status of sensors 21 to 31
• Alarm status of sensors 21 to 31
• Internal temperature value of sensors 21 to 31
• Segment current temperature value of sensors 21 to 31
A-3-2
Using the CS/CJ-series
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......