A - 3
Appendices
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
A-
1 Spec
ificat
ions
A
A-1-
1 Main Unit Specifications
Main Unit Characteristics
Model
K6PM-THMD-EIP
Item
Temperature measurement range
The temperature measurement range is described in the temperature
sensor (K6PM-THS3232) performance.
Measurement temperature accuracy
The measurement temperature accuracy is described in the temperature
sensor (K6PM-THS3232) performance.
Sampling cycle for the sensor
Approx. 1 second per Unit
External
trigger
External contact input
specifications
Short circuit: Residual voltage 1.5 V max.
Open: Leakage current 0.1 mA max.
Short circuit current
Approx. 7 mA
Alarm
Measurement parame-
ters
Current temperature, differential temperature, sensor internal tempera-
ture
Expression method
Transistor output, alarm bar display
Number of variables
Two threshold values per segment (Threshold 1 and Threshold 2)
Threshold setting
range
0.0 to 999.9°C (0.0 to 999.9°F)
Hysteresis
3.0°C width (5.4°F width)
Resetting method
Manual resetting
*1
or automatic resetting (switching)
*1. Manual resetting method: Press and hold the
SEG/ALM RST
Button
LCD display
7-segment digital displays and individual indicators
Display resolution
0.1°C
Applicable
standards
Approved standards
UL61010-1 (listing) installation location: Pollution degree 2, Korean Radio
Waves Act
Conforming standards
RCM
EMC
EN61326-1 (EMI: Class A EMS: Industrial Location)
Recommended fuse
T2A, time lag, shut-off capacity
Insulation resistance
20 M
Ω
min.
Between all external terminals and the case
Between all power supply terminals and all other terminals
Between all RS-485 communications terminals, and all external trigger
input terminals, all transistor output terminals and all Ethernet ports
Dielectric strength
2,000 VAC for 1 minute
Between all external terminals and the case
Between all power supply terminals and all other terminals
Between all RS-485 communications terminals, and all external trigger
input terminals, all transistor output terminals and all Ethernet ports
Vibration resistance
Frequency: 10 to 55 Hz, 0.35-mm single amplitude in X, Y, and Z direc-
tions (10 sweeps of 5 min each)
Shock resistance
150 m/s
2
, 3 times each in X, Y, and Z axes, 6 directions
Degree of protection
IP20
Warranty period
1 year
Indicators
Alarm bar
Red, yellow, and green
MS and NS
Red and green
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......