6 Monitoring and Setting with the Modbus TCP
6 - 12
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
0190 hex
K6PM-TH sensor 1 pixel
current temperature value
5
Temperature data of each pixel from 320 to
383 pixels of the K6PM-TH sensor.
128
R
01D0 hex
K6PM-TH sensor 1 pixel
current temperature value
6
Temperature data of each pixel from 384 to
447 pixels of the K6PM-TH sensor.
128
R
0210 hex
K6PM-TH sensor 1 pixel
current temperature value
7
Temperature data of each pixel from 448 to
511 pixels of the K6PM-TH sensor.
128
R
0250 hex
K6PM-TH sensor 1 pixel
current temperature value
8
Temperature data of each pixel from 512 to
575 pixels of the K6PM-TH sensor.
128
R
0290 hex
K6PM-TH sensor 1 pixel
current temperature value
9
Temperature data of each pixel from 576 to
639 pixels of the K6PM-TH sensor.
128
R
02D0 hex
K6PM-TH sensor 1 pixel
current temperature value
10
Temperature data of each pixel from 640 to
703 pixels of the K6PM-TH sensor.
128
R
0310 hex
K6PM-TH sensor 1 pixel
current temperature value
11
Temperature data of each pixel from 704 to
767 pixels of the K6PM-TH sensor.
128
R
0350 hex
K6PM-TH sensor 1 pixel
current temperature value
12
Temperature data of each pixel from 768 to
831 pixels of the K6PM-TH sensor.
128
R
0390 hex
K6PM-TH sensor 1 pixel
current temperature value
13
Temperature data of each pixel from 832 to
895 pixels of the K6PM-TH sensor.
128
R
03D0 hex
K6PM-TH sensor 1 pixel
current temperature value
14
Temperature data of each pixel from 896 to
959 pixels of the K6PM-TH sensor.
128
R
0410 hex
K6PM-TH sensor 1 pixel
current temperature value
15
Temperature data of each pixel from 960 to
1,023 pixels of the K6PM-TH sensor.
128
R
0450 hex
:
04FE hex
Reserved
0000 hex is returned.
350
R
04FF hex
Illegal address
Exception code 02 hex (illegal data
address) is returned.
----
----
*1. R: Read using Reading of multiple registers (03 hex).
*2. A hexadecimal value in the range of 0.0 to 80.0°C (32.0 to 176.0°F).
(Example: C8 in the case of 20.0°C)
6-3-3
Main Unit Setting
Address
Parameter name
Description
Initial value
Number
of bytes
R/W
*1
A000 hex
Alarm latch
0: Disable (no latch)
1: Enable (with latch)
0001 hex
2
R/W
Address
Parameter name
Description
Number of
bytes
R/W
*1
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......