5 Monitoring and Setting with the EtherNet/IP Communications
5 - 20
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
This object sets the alarm threshold of the Main Unit.
Specify 378 hex.
Specify the following data according to the target.
• For class: Specify 00 hex.
• For instance: Specify 01 to 1F hex (compatible with sensor number 1 to 31).
Specify the information to write.
Class Attribute ID
None
Instance Attribute ID
The instance attribute ID specifies the per-instance attribute.
The setting parameter is enabled after the power supply is reset.
An example of a case where the instance ID is 01 hex is described below.
5-3-6
K6PM-TH Sensor Alarm Setting Object (Class ID: 378 hex)
Service Codes
Service
code
Service name
Description
Supported services
Classes
Instances
01 hex
Get_Attributes_All
Reads the values of all attributes.
Not supported
Supported
02 hex
Set_Attributes_All
Write values to all attributes.
Not supported
Supported
0E hex
Get_Attribute_Single Reads the value of the specified attribute.
Not supported
Supported
10 hex
Set_Attribute_Single
Write the value of the specified attribute.
Not supported
Supported
Class ID
Instance ID
Attribute ID
Attribute ID
Parameter name
Description
Attribute
Data
Data type
Default
value
64 hex
Sensor 1
Internal temperature alarm
setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
01C2 hex
(45.0)
65 hex
Sensor 1
Internal temperature alarm
setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
0226 hex
(55.0)
66 hex
K6PM-TH sensor 1 seg-
ment 0
Current temperature alarm
setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
02BC hex
(70.0)
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......