5 Monitoring and Setting with the EtherNet/IP Communications
5 - 14
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
• K6PM-TH sensor alarm status per sensor
This object reads the current temperature value of each pixel of each sensor of the Main Unit for each
segment (64 pixels). The current temperature value of the read pixel is saved in an array variable hav-
ing 64 elements.
Specify 376 hex.
Specify the following data according to the target.
• For class: Specify 00 hex.
• For instance: Specify 01 to 1F hex (compatible with sensor number 1 to 31).
Bit position
Status
Bit contents
0
1
0
Internal temperature alarm (threshold 1 exceeded)
Not occurred
Occurred
1
Internal temperature alarm (threshold 2 exceeded)
Not occurred
Occurred
2
Current temperature alarm (threshold 1 exceeded)
Not occurred
Occurred
3
Current temperature alarm (threshold 2 exceeded)
Not occurred
Occurred
4
Differential temperature alarm (threshold 1 exceeded)
Not occurred
Occurred
5
Differential temperature alarm (threshold 2 exceeded)
Not occurred
Occurred
6
Internal predicted arrival time temperature alarm (threshold
value 1 exceeded)
Not occurred
Occurred
7
Internal predicted arrival time temperature alarm (threshold
value 2 exceeded)
Not occurred
Occurred
8
Predicted arrival time temperature alarm (threshold value 1
exceeded)
Not occurred
Occurred
9
Predicted arrival time temperature alarm (threshold value 2
exceeded)
Not occurred
Occurred
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
5-3-4
K6PM-TH Sensor Temperature Monitor Object (Class ID: 376 hex)
Service Codes
Service code
Service name
Description
Supported services
Classes
Instances
0E hex
Get_Attribute_Single
Reads the value of the
specified attribute.
Not supported
Supported
Class ID
Instance ID
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......