5 - 7
5 Monitoring and Setting with the EtherNet/IP Communications
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5
-2 Mo
nito
ring
Using
th
e T
ag
Dat
a Lin
k
5
5-
2-2 Setting the
Assemb
ly Ob
ject
For details on the data, refer to
5-3 Monitoring and Setting Using the CIP Message Communications
and Examples of Communications Instructions
5-2-2
Setting the Assembly Object
Parameter name Setting value
Remarks
Function
Instance ID
64 hex
(Input_100)
Output connection
(Size: 128 bytes)
• K6PM-TH status
• Running time data
• Status of sensors 1 to 31
• Alarm status of sensors 1 to 31
65 hex
(Input_101)
Output connection
(Size: 380 bytes)
• Status of sensors 1 to 10
• Alarm status of sensors 1 to 10
• Internal temperature value of sensors 1 to 10
• Segment current temperature value of sensors 1 to 10
66 hex
(Input_102)
Output connection
(Size: 380 bytes)
• Status of sensors 11 to 20
• Alarm status of sensors 11 to 20
• Internal temperature value of sensors 11 to 20
• Segment current temperature value of sensors 11 to 20
67 hex
(Input_103)
Output connection
(Size: 418 bytes)
• Status of sensors 21 to 31
• Alarm status of sensors 21 to 31
• Internal temperature value of sensors 21 to 31
• Segment current temperature value of sensors 21 to 31
5-2-3
Assigning the Assembly Instance
Instance ID: 64 hex
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
+0
Main Unit status
Refer to "Main Unit status" described later.
+1
Running time data
+2
K6PM-TH sensor 1 status
Refer to "K6PM-TH sensor status per sensor" in
5-3-3 K6PM-TH Sensor Monitor Object (Class ID:
on page 5-12 described later.
+3
K6PM-TH sensor 1 alarm status
Refer to "K6PM-TH sensor alarm status per sensor" in
5-3-3 K6PM-TH Sensor Monitor Object (Class
on page 5-12 described later.
+4
K6PM-TH sensor 2 status
+5
K6PM-TH sensor 2 alarm status
+6
K6PM-TH sensor 3 status
+7
K6PM-TH sensor 3 alarm status
:
:
:
:
:
:
:
:
+62
K6PM-TH sensor 31 status
+63
K6PM-TH sensor 31 alarm status
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...