5 - 3
5 Monitoring and Setting with the EtherNet/IP Communications
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5-1
Ou
tlin
e
5
5-1-2 EtherNet/IP
Communi
cations Specificatio
ns
Multiple data such as measured values of the Main Units are periodically sent to the specified area of
the PLC. The K6PM-TH can perform tag data link communications over four connections.
• PLC-side input tag set
The I/O memory address or variables are assigned. The data sizes of the four segments are 128 bytes,
380 bytes, 380 bytes, and 418 bytes (K6PM-TH internal data sizes), for a total of 1306 bytes.
• Main Unit-side output tag set
The Main Unit assigns the instance ID of the internal data to be tagged data link. The data sizes are 128
bytes, 380 bytes, 380 bytes, and 418 bytes for a total of 1306 bytes.
Configuration Tool
When configuring with OMRON controllers, the following setting tools for the tag data link should be
used.
A CIP client such as the NJ/NX-series issues any CIP command in the Explicit message to the Main
Units. This allows you to read and write all the data of the Main Unit.
Communications Instructions
When sending a CIP command with Explicit messages from OMRON PLCs or Controllers, use the
following communications Instruction.
Tag Data Link
Configurations
Tag data link setting tool (configuration tool) to be used
CS/CJ-series
Network Configurator
NJ/NX-series
Network Configurator
or
Sysmac Studio
CIP Message Communications
Configurations
Communications Instruction
CS/CJ-series
• Explicit message send commands (2810 hex) for CIP routing are issued by
CMND instructions
NJ/NX-series
• CIPSend (Send Explicit Message Class 3) instruction
Or
• CIPUCMMSend (Send Explicit Message UCMM) instruction
5-1-2
EtherNet/IP Communications Specifications
Item
Specification
Tag data link
Class1
Connection resource: 4 max.
Packet interval (RPI)
1,000 to 10,000 ms
Timeout value
Multiples of RPI (4 times, 8 times, 16 times,
…, and 512 times)
Connection type
Point To Point Connection (fixed)
Explicit message
Class 3
Number of clients that can communicate at
one time: 2 max.
UCMM
Number of clients that can communicate at
one time: 2 max.
Conformance
EtherNet/IP conformance test
Conforms to CT16
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......