background image

English

USER'S MANUAL

(1) Handle with care

Do not drop G9SX to the ground or expose to excessive vibration or 

mechanical shocks. G9SX may be damaged and may not function properly.

(2) Conditions of storage

Do not store in such conditions stated below.

1) In direct sunlight

2) At ambient temperatures out of the range of -10 to 55 °C

3) At relative humidity out of the range of 25% to 85% or under such 

temperature change that causes condensation.

4) In corrosive or combustible gases

5) With vibration or mechanical shocks out of the rated values.

6) Under splashing of water, oil, chemicals

7) In the atmosphere containing dust, saline or metal powder.

G9SX may be damaged and may not function properly.

(3) Mounting

Mount G9SX to DIN rails with attachments (TYPE PFP-M, not 

incorporated to this product), not to drop out of rails by vibration etc. 

especially when the length of DIN railing is short compared to the widths of G9SX.

(4) Following spacing around G9SX should be available to apply rated 

current to outputs of G9SX and for enough ventilation and wiring:

a) At least 25 mm beside side faces of G9SX.

b) At least 50 mm above top face of G9SX and below bottom face of G9SX.

(5) Wiring

1) For model G9SX-

Use the following to wire to G9SX-

.

-Solid wire: 0.2 to 2.5mm

2

  AWG24 to AWG12

-Stranded wire (Flexible wire): 0.2 to 2.5mm

2

 AWG24 to AWG12 

Strip the cover of wire no longer than 7mm.

2) For model G9SX-

-RT (with screw terminals)

Tighten each screw with a specified torque of 0.5 to 0.6N·m, or the 

G9SX-

 may malfunction or generate heat.

3) For Logical AND Connection

Use VCTF cable or shielded cable for Logical AND connection 

between units.

(6) When connecting Expansion Units (G9SX-EX

-

) to Advanced Unit:

1) Follow the procedure below:

a) Remove the termination connector from the receptacle on 

Advanced Unit,

b) Insert the head of the connecting cable of Expansion Unit to the 

receptacle on the Advanced Unit 

c) Set the termination connector to the receptacle on the Expansion Unit 

at the end position. When Advanced Unit is used without expansion 

units, leave the termination connector set on the Advanced Unit.

2) Do not remove the termination connecter while the system is operating.

3) Before applying supply voltage, confirm that the connecting 

sockets and plugs are locked firmly.

4) All of the Expansion Units should be supplied with its specified 

voltages within 10s after the connected Advanced Unit is supplied 

with voltage.

Otherwise, Advanced Unit detects the power-supply error for the 

Expansion Units.

(7) Use cables with length less than 100m to connect to Safety Inputs, 

Feed-back/Reset inputs, or between Logical AND connection inputs 

and Logical connection outputs, respectively. 

(8) Set the time duration of OFF-delay to an appropriate value that does 

not cause the loss of safety function of system.

(9) Logical connection between Units:

1) When using Logical AND connection inputs, set the Logical 

connection preset switch to 'AND' position for the units which the 

logical connection signal are input to.

2) Connect Logical connection outputs appropriately to Logical AND 

connection inputs of the relevant unit. Verify the operation of G9SX 

before commissioning the system.

3) When configuring the safety related system, be sure to consider 

that the delay of response time caused by logical connections do 

not degrade the safety function of the system.

(10) To determine safety distance to hazards, take into account the delay 

of Safety outputs caused by the following time:

1) Response time of Safety inputs

2) Response time of Logical AND connection input

(See also "Ratings and specifications, note5")

3) Preset  off-delay time

4) Accuracy of off-delay time

(11) Start entire system after more than 5s have passed since applying 

supply voltage to all G9SXs in the system.

(12) G9SX may malfunction due to electro-magnetic disturbances. 

Be sure to connect the terminal A2 to ground.

When using a DC power supply with light curtains, use DC power 

supply which has no interruption by a power failure of 20ms.

(13) Devices connected to G9SX may operate unexpectedly. 

When replacing G9SX, disconnect it from power supply.

(14) Adhesion of solvent such as alcohol, thinner, trichloroethane or 

gasoline on the product should be avoided. Such solvents make the 

marking on G9SX illegible and cause deterioration of parts.

(15)This is a class A product. In residential areas it may cause radio

      interference, in which case the user may be required to take

      adequate measures to reduce interference.

(16) Operate the reset input more than 0.4 seconds immediately after the 

safety outputs are OFF.

G9SX does not accept the reset input from when the outputs are 

turned ON and until 0.4 seconds passes after the outputs are turned 

OFF.

25mm min.

25mm min.

A2

X2

44

34

24

14

A1

33

43

13

23

No.

G9SX-EX041-T
24VDC

A2

X2

44

34

24

14

A1

33

43

13

23

No.

G9SX-EX041-T
24VDC

G9SX-BC202
24VDC

No.

T1

T2

FB

ERR

EI

PWB

L2

L1

S24

S14

A2

X2

T22

T21

A1

X1

T12

T11

Y1

T32 T33

T31

No.

OFF-DELAY

0.5

0.4

0.3

0.2

15

10

7

5

4

3

2

1.5

1

0.6

0.7

0

S54

S44

S34

S24

S14

L1

A2

T42

T41

T22

T21

A1

X2

X1

Y1

T12

T11

T33

T31

T1

ERR

EI

AND

FB

ED

T2

PWR

T32

G9SX-AD322-T15
24VDC

50mm min.

50mm min.

ED

PWR

ED

PWR

ERR

ERR

0.5

0.4

0.3

0.2

15

10

7

5

4

0.6

0

3

0.7

OFF-DELAY

AND

OFF

T41/T42

Appearance and Explanation of 
Each Parts

1

Type G9SX-BC202-

 (Basic Unit)

Type G9SX-AD322-T

-

 (Advanced Unit)

No.

OFF-DELAY

0.5

0.4

0.3

0.2

15

10

7

5

4

3

2

1.5

1

0.6

0.7

0

S54

S44

S34

S24

S14

L1

A2

T42

T41

T22

T21

A1

X2

X1

Y1

T12

T11

T33

T31

T1

ERR

EI

AND

FB

ED

T2

PWR

T32

G9SX-AD322-T15
24VDC

Safety
Input1

Auxiliary Monitor output

Aixiliary Error output

Logical AND connection outputs

Safety solid-state outputs

Cross fault detection mode input

Feedback/Reset input

Power )

Power Supply(-)

Safety
Input2

Logical AND 
connection output

Power Supply(-)

Power )

Logical AND
connection input

Termination
Connector

Off-delay
time preset
switch

Feedback/Reset input

Auxiliary
Monitor output

Auxiliary
Error output

Cross fault detection
mode input

Safety
Input2

Safety
solid-
state outputs

Safety
Input1

Off-delayed Safety solid-state outputs

Logical AND
connection
preset switch

G9SX-BC202
24VDC

No.

T1

T2

FB

ERR

EI

PWR

L2

L1

S24

S14

A2

X2

T22

T21

A1

X1

T12

T11

Y1

T32 T33

T31

Indicator

Settings indication 

(at power on)

Items

Setting
position

indicator
status

Setting mode

Setting
status

Y1 terminal

T32 or T33
 terminal

light up

not lit

detection mode

non-detection mode

Y1 =  open

Y1 = 24VDC

light up

not lit

manual reset mode

auto reset mode

T33 = 24VDC

T32 = 24VDC

light up

not lit

enable Logical AND input

disable Logical AND input

'AND'

'OFF'

Logical AND 

connection 

preset switch

T1

FB

AND

Cross fault 

detection 

mode

Logical AND 

connection 

input mode

Reset 

mode

Settings for G9SX can be checked by indicators for approx. 3 seconds 

after power on.

During the settings indication term, ERR indicator will light up,

however the auxiliary error output will remain off.

Marking

LED Indicators

Color

Name

Function

Power Supply

Indicator
Error Indicator

Safety input #1 
Indicator

- Blinks when error relating to Safety  

input #1 occurrs. (*1)

- Lights up while high signal is input to T12

- Lights up or blinks corresponding to the 

occurring error (*1)

- Lights up while power is supplied.

Safety input #2 
Indicator

- Blinks when error relating to Safety  

input #2 occurrs. (*1)

- Lights up while high signal is input to T22

Logical AND 
input Indicator

-- With automatic reset while high signal is 

input to T33

- Lights up in the following cases:

- Lights up while high signal is input to T41.

- Blinks when error relating to Logical 

AND connection Input occurrs. (*1)

-- With manual reset while hgh signal is 

input to T32.

- Blinks when an error relating to 

Feedback/Reset  input occurrs. (*1)

Safety output
indicator

- Blinks when an error relating to Safety 

solid-state output occurrs. (*1)

- Lights up while Safety solid-state outputs 

(S14, S24, S34) are in ON-state.

Off-delayed
Safety output
Indicator

- Blinks when an error relating to Safety 

off-delayed solid-state output occurrs.(*1)

- Lights up while Safety off-delayed solid- 

state outputs (S44, S54) are in ON-state.

Feedback/Reset 
input Indicator

PWR

ERR

T1

T2

AND

EI

ED

FB

Green

Red

Orange

Orange

Orange

Orange

Orange

Orange

Type G9SX-AD322-T

-

 (Advanced Unit)

Type G9SX-BC202-

 (Basic Unit)

Internal Connection

2

*1 Internal power supply circut is not isolated.

*2 Logical AND input is isolated.

*3 The Safety solide-state outputs,S14 - S54, are internally redundant, respectively.

*3

*1

*1

*2

*2

*1 Internal power supply circut is not isolated.

*2 The Safety solide-state outputs,S14 and S24, are internally redundant, respectively.

S14

A2

S24 S34 S44 S54 L1 X1 X2

Power
supply

circuit

Safety

Input 1

Safety

Input 2

Safety outputs control

Auxiliary outputs

control

Reset/Feedback

Input

Logical AND input

Expansion Unit

outputs control

T11

A1

T12 T21 T22 T31 T32 T33 Y1

T41 T42

S14

A2

S24

L1 L2

X1 X2

Power
supply

circuit

Safety

Input 1

Safety

Input 2

Safety outputs control

Auxiliary outputs

control

Reset/Feedback

Input

T11

A1

T12 T21 T22 T31 T32 T33 Y1

Cross fault

detectiaon

mode in

Cross fault

detectiaon

mode in

Name
Logical AND 

Connection 

Preset Switch
Off-delay Time 

Preset Switch

Function
Sets Logical AND 

Connection Inputs to 

valid or invalid. (*2)
Presets Off-delay time

(duplicate) (*3), (*4)

State/Value (position of switch)
OFF (Invalid: default setting)/
AND (valid)

For Type G9SX-AD322-T150-

0 (default setting value) 

/10/20/30/40/50/60/70/80/90/100/

110/120/130/140/150 (s) (*5)

For Type G9SX-AD322-T15-

0 (default setting value) 

/0.2/0.3/0.4/0.5/0.6/0.7/1/1.5/2/

3/4/5/7/10/15 (s) (*5)

Note:

(*1) See 7 Fault Detection for details.

(*2) When operating G9SX using Logical AND Connection function, be sure to 

set the preset switch to AND (valid) position for the units which the logical 

input signal is input to. When the switch is set to OFF (invalid) position, it is 

detected as a fault.

(*3) Set both of the two Off-delay Time Preset Switches, one each on the front 

and back, to the same value.

(*4) Off-delay time duration of Expansion Unit (OFF-delay model) synchronize 

with the OFF-delay time duration set by Off-delay Time Preset Switch of 

Advanced Unit.

(*5) See following illustration for setting position of Off-delay Time Preset Switch. 

Make sure that the direction of cutting edge of preset switch is correctly 

pointed to the off-delay time value which must be set.

Change the value of the preset switches only when G9SX is disconnected 

from power supply.

The states of the preset switches come into effect when the power supply to 

G9SX turns on.

OFF-DELAY

0.5

0.4

0.3

0.2

15

10

7

5

4

3

2

1.5

1

0.6

0.7

0

OFF-DELAY

0.5

0.4

0.3

0.2

15

10

7

5

4

3

2

1.5

1

0.6

0.7

0

cutting edge

ex.1) 0 second off-delay setting

ex.2) 1 second off-delay setting

Preset Switches

 (only applies to TYPE G9SX-AD322-T

-

)

Type G9SX-AD322-T

-

Type G9SX-BC202-

(Advanced Unit)
(Basic Unit)

Basic Unit

Advanced Unit

Dimensions

3

No.

OFF-DELAY

0.5

0.4

0.3

0.2

15

10

7

5

4

3

2

1.5

1

0.6

0.7

0

S54

S44

S34

S24

S14

L1

A2

T42

T41

T22

T21

A1

X2

X1

Y1

T12

T11

T33

T31

T1

ERR

EI

AND

FB

ED

T2

PWR

T32

G9SX-AD322-T15
24VDC

100 max.

115 max.

35.5 max.

23 max.

(22.5)*

*Note1 Above outline drawing is for -RC terminal type.

*Note2 For -RC terminal type only.

Typical dimension

(35)*

G9SX-BC202
24VDC

No.

T1

T2

FB

ERR

EI

PWR

L2

L1

S24

S14

A2

X2

T22

T21

A1

X1

T12

T11

Y1

T32 T33

T31

(10)

*Note2

*Note2

(6)

(6)

Ratings and Specifications

4

Ratings

Specifications and Performance

Isolation specifications

Rated supply voltage

Power

Item

input

Outputs

24VDC

TYPE G9SX-AD322-T

-

3 W Max.

TYPE G9SX-BC202-

-15% to +10% of rated supply voltage
4 W Max.
P channel MOS FET output
Load current:

Using 2 outputs or less: 1A DC Max.

Using 3 outputs or more: 0.8A DC Max.

(See Note4)

Load current:

Using 1 output: 1A DC Max.

Using 2 outputs: 0.8A DC Max.

(See Note4)

PNP transistor output

Load current: 100mA Max.

Operating voltage range
Rated power consumption 

(See Note1)

Safety solid-state output 

(See Note3)

Off-delayed safety solid-state output 

(SeeNote3)

Auxiliary output

Item

TYPE G9SX-AD322-T

-

TYPE G9SX-BC202-

50 ms Max.(Safety input)

II
50ms Max. (Safety input)

100ms Max. (Logical AND connection input)
15 ms Max. 

(See Note5)

10 mA min.
11 V min.
5 V min.
1 mA max.

100 ms min.

3.0 V max. (safety output, auxiliary output)
0.1 mA max. (safety output, auxiliary output)

100 m max.

(External connection impedance: 100ohm max. and 10 nF max.)

Over voltage category (IEC/EN 60664-1)
Operating time (OFF to ON state)

(See Note5,6)

Response time (ON to OFF state)

Input current
ON voltage
OFF voltage
OFF current
Maximum wiring length

Input

Output

-

Approx. 125 g

Within plus or minus 5% of the set value

Frequency: 10 to 55 to 10Hz,

Amplitude: 0.375mm half amplitude (0.75mm double amplitude)
300 m/s

2

 (destruction), 100 m/s

2

 (malfunction)

-10 to +55     (No freezing or condensation)
25 to 85 %RH
0.5Nm (Applicable only to TYPEG9SX-

-RT: screw terminal model)

Approx. 200g

100m Max.

(Permissible impedance of inputs : 100ohm Max and 10nF Max)

Maximum cable length for Logical connection input

and Safety inputs

4 units Max. 

(See Note7)

Number of units connected per one Logical connection output.

20 units Max. 

(See Note7,8)

Total number of units connected with Logical connection

5 units Max. 

(See Note8)

Number of units connected in series with Logical connection
Accuracy of Off-delay time

100ms Min.

Reset input time
Vibration resistance

Mechanical shock resistance
Ambient temperature
Ambient humidity
Terminal tightening torque
Weight

Item

TYPE G9SX-AD322-T

-

TYPE G9SX-BC202-

500VAC for 1min

20Mohm Min.

(by 100VDC megger)

20Mohm Min.

(by 100VDC megger)

20Mohm Min.

(by 100VDC megger)

500VAC for 1min

500VAC for 1min

Insulation resistance

Dielectric strength

- Between all terminals connected together 

and DIN rail.

- Between Logical AND connection terminals, 

and

Power supply input terminals and other input 

and output terminals connected together. 

-

-

- Between all terminals connected together 

and DIN rail.

- Between Logical AND connection terminals, 

and

Power supply input terminals and other input 

and output terminals connected together. 

Suitability for Use 

Omron Companies shall not be responsible for conformity with any standards,

codes or regulations which apply to the combination of the Product in the

Buyer’s application or use of the Product. At Buyer’s request, Omron will

provide applicable third party certification documents identifying ratings and

limitations of use which apply to the Product. This information by itself is not

sufficient for a complete determination of the suitability of the Product in

combination with the end product, machine, system, or other application or

use. Buyer shall be solely responsible for determining appropriateness of the

particular Product with respect to Buyer’s application, product or system.

Buyer shall take application responsibility in all cases.

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS

RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT 

ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO 

ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY 

RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL 

EQUIPMENT OR SYSTEM.

OMRON Corporation 

 (Manufacturer)

 Contact:  www.ia.omron.com

Regional Headquarters

Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN

OMRON EUROPE B.V. (Importer in EU)

Wegalaan 67-69, 2132 JD Hoofddorp

The Netherlands

Tel: (31)2356-81-300/Fax: (31)2356-81-388

OMRON ELECTRONICS LLC

2895 Greenspoint Parkway, Suite 200 

Hoffman Estates, IL 60169 U.S.A.

Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD.

No. 438A Alexandra Road # 05-05/08 (Lobby 2), 

Alexandra Technopark, 

Singapore 119967

Tel: (65) 6835-3011/Fax: (65) 6835-2711

OMRON (CHINA) CO., LTD.

Room 2211, Bank of China Tower, 

200 Yin Cheng Zhong Road, 

PuDong New Area, Shanghai, 200120, China

Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200

Reset input time
ON-state residual voltage
OFF-state leakage current

Flexible Safety Unit

0631677-2 G

Thank you for purchasing G9SX Flexible Safety Unit.

Please read and understand this manual before 
using the products.
Keep this manual ready to use whenever needed.
Only qualified person trained in professional 
electrical technique should handle G9SX.

Please consult your OMRON representative if you 
have any questions or comments.
Make sure that information written in this document are 
delivered to the final user of the product.

Type G9SX-AD322-T

-

Type G9SX-BC202-

Safety Precautions

Indicates a potentially hazardous situation 
which, if not avoided, will result in minor or 
moderate injury, or may result in serious 
injury or death. 
Additionally there may be significant 
property damage.

Meanings of Signal Words

The following signal words are used in this manual.

Alert Statements

Serious injury may possibly occur due to breakdown of 

safety outputs.

Do not connect loads beyond the rated value to the safety 

outputs.

Serious injury may possibly occur due to loss of required 

safety functions.

Wire G9SX properly so that supply voltages or voltages 

for loads do NOT touch the safety inputs accidentally or 
unintentionally.

Serious injury may possibly occur due to damages of 

safety inputs.

Apply protection circuitry against back electromotive force 

in case connecting inductive loads to safety outputs.

Serious injury may possibly occur due to loss of safety 

functions.

Use appropriate devices referring to the information 

shown below.

Indicates prohibited actions

Meaning of Alert Symbols

The following alert symbols are used in this manual.

Indicates mandatory actions

WARNING

WARNING

Controlling 

Devices

Emergency 

stop switch

Door 

interlocking

switch 

Limit switch

Safety Sensor

Relay with 

forcibly guided 

contacts

Contactor

Other devices

Requirements

Use approved devices with Direct Opening 

Mechanism complying with IEC/EN 60947-5-1

Use approved devices with Direct Opening

Mechanism complying with IEC/EN 60947-5-1 

and capable of switching micro loads of 24VDC, 

5mA.

Use approved devices complying with the 

relevant product standards, regulations and 

rules in the country where it is used.
Use approved devices with forcibly guided 

contacts complying with IEC 61810-3 (EN 50205).

For feedback purpose use devices with contacts 

capable of switching micro loads of  24VDC, 5mA.
Use approved devices complying with IEC/EN 

60947-4-1 auxiliary contact linked with power 

contact (mirror contact).

For feedback purpose use devices with contacts 

capable of switching micro loads of 24 VDC, 5 mA.

Evaluate whether devices used are appropriate 

to satisfy the requirements of safety category level.

(1) Use G9SX within an enclosure with IP54 protection or higher of IEC/EN60529

(2) Incorrect wiring may lead to loss of safety function. Wire conductors correctly 

and verify the operation of G9SX  before commissioning the system in which 

G9SX is incorporated. 

(3)  Do not apply DC voltages exceeding the rated voltages, nor any AC voltages 

to G9SX. Do not connect to DC distribution network.

(4)  Use DC supply satisfying requirements below to prevent electric shock.

- DC power supply with double or reinforced insulation, for example, 

according to IED/EN60950 or EN50178 or a tranceformer according to 
IEC/EN61558.

- DC supply satisfies the requirement for class 2 circuits orlimited 

voltage/current circuit stated in UL 508.

(5)  Apply properly specified voltages to G9SX inputs.

Applying inappropriate voltages cause G9SX to fail to perform its specified 

function, which leads to the loss of safety functionsor damages to G9SX

(6)  Auxiliary error outputs and auxiliary monitoring outputs are NOT safety outputs.

Do not use auxiliary outputs as any safety output.

Such incorrect use causes loss of safety function of G9SX and its relevant system.

Also Logical connection outputs can only be used for logical connections 

between G9SXs.

(7) After installation of G9SX, qualified personnel should confirm the installation, 

and should conduct test operations and maintenance.

The qualified personnel should be qualified and authorized to secure the 

safety on each phases of design, installation, running, maintenance and 

disposal of system.

(8)  A person in charge, who is familiar to the machine in which G9SX is to be 

installed, should conduct and verify the installation.

(9) Turn OFF the signal to Safety input or Logical AND connection input every 

24hours and make sure G9SX operates without faults by checking the state 

of the ERR indicator.

(10) Do not dismantle, repair, or modify G9SX.  It may lead to loss of its safety 

functions.

(11) Use only appropriate components or devices complying with relevant safety 

standards corresponding to the required level of safety categories. 

Conformity to requirements of safety category is determined as an entire system. 

It is recommended to consult a certification body regarding assessment of 

conformity to the required safety level.

(12) OMRON shall not be responsible for conformity with any safety standards 

regarding to customer's entire system.

Precautions for Safe Use

typ.100ms

OFF

ON

360 µm 

Max.

G9SX-BC or

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

G9SX-AD

Total number of units connected with 
Logical connection : 20 units Max.

Number of units connected 
in series with Logical 
connection : 5 units Max.

Number of units connected 
per one Logical connection 
output : 4 units Max.

* Note
 For G9SX-AD322-T

-

, one Logical output is available.

Note:

(1) Power consumption of loads not included .

(2) Ensure that the current exceeds the minimum applicable load of the 

device connected.

(3) While safety outputs are at its ON state, signal sequence shown 

below is output continuously for diagnosis.

When using the safety outputs as input signals to control devices

(e.i. programmable controller), consider the off pulse below.

(4) The following derating is required when Units are mounted side-by-side.

G9SX-AD322-

 /G9SX-BC202-

 : 0.4 A max. load current

(5) When multiple units are connected by logical connection, the total 

operating/response time is an accumulation of the 

operating/response timeconnected.

(6) Required time for safety solid-state output to turn ON, after 

necessary inputs turn ON.

(7) For details of the system with logical connection refer to the 

illustration below.

(8) The number of TYPE G9SX-EX401-

 (Expansion Unit) and TYPE 

G9SX-EX041-T-

 (Expansion Unit, Off-delayed model) not included.

Precautions for Correct Use

Original instructions

(13) Disconnect G9SX from power supply when wiring. Devices connected to 

G9SX may operate unexpectedly.

(14) Be cautious not to have your fingers caught when attaching terminal sockets 

to the plugs on G9SX.

EU Declaration of Conformity

Standards

OMRON declares that G9SX is in conformity with the 
requirements of the following EU Directives:
 

EMC Directive 2014/30/EU

 

Machinery Directive 2006/42/EC

G9SX is designed and manufactured in accordance with 
the following standards:
 

EN ISO13849-1:2015 Category 4 PL e,

 

IEC/EN61508 SIL3,

  IEC/EN61000-6-2, IEC/EN61000-6-4,  
 UL508, 

  UL1998,

 

CAN/CSA C22.2 No.142

© OMRON Corporation 2005-2020 All Rights Reserved.