Operation manual
G9SR
XXII
REGULATIONS
AND
STANDARDS
The G9SR Safety Relays conform to the requirements in compliance with the following
standards:
Certifying body
Standards
TÜV SUED
•
EN ISO 13849-1:2008
•
EN 61508 parts 1-4:2010
•
IEC/EN 62061/A1 2013
•
IEC 61496-1/A1 2008 Type 4
Others
•
CE Marking
•
CSA Marking
The G9SR Safety Relays are applicable in applications up to Performance level e.
The hardware is designed according to the requirements for a category 4 system.
Do not use the G9SR Safety Relays in situations where the risk assessment requires
higher values than mentioned in the following table:
Pl
e
EN ISO 13849-1:2008
Cat.
4
EN ISO 13849-1:2008
Type
4
IEC 61496-1: ed 2 2004
PFHd G9SR-BC
5.7*10
-9
EN ISO 13849-1:2008
PFHd G9SR-AD
5.7*10
-9
EN ISO 13849-1:2008
PFHd G9SR-EX
3.1*10
-9
EN ISO 13849-1:2008
MTTFD G9SR-BC
351 Year
EN ISO 13849-1:2008
MTTFD G9SR-AD
379 Years
EN ISO 13849-1:2008
MTTFD G9SR-EX
1120 Years
EN ISO 13849-1:2008
DCavg
97%
EN ISO 13849-1:2008
SIL
3
EN 61508:2010
Proof test interval :
20yr
IEC 62061: 2005
MTTR
8h
EN61508-1:2008
Type
Type B
EN61508:2010
HFT
1
EN61508:2010
Using a G9SR Safety Relay enables building a safety control system that satisfies the
following:
•
Requirements for SIL 3 (Safety Integrity Level 3) in EN 61508, IEC/EN 62061,
Safety Standard for Safety Instrumented Systems (Functional Safety of Electrical/
Electronic/Programmable Electronic Safety-related Systems)
•
Requirements for PLe (Performance Level e)
and for safety category 4 in EN ISO13849-1
Summary of Contents for G9SR
Page 1: ...ZX T Series Cat No J12E EN 03 G9SR Safety Relays OPERATION MANUAL G9SR BC G9SR AD G9SR EX...
Page 34: ...Operation manual G9SR Page 8 of 79 3 1 Test the OFF behaviour...
Page 35: ...Operation manual G9SR Page 9 of 79 3 2 Test the ON behaviour...
Page 102: ...Operation manual G9SR Page 76 of 79 My notes...
Page 105: ...Operation manual G9SR Page 79 of 79 My notes...