G3PW Constant-current Models can perform serial communications with EJ1
Modular Temperature Controllers or SYSMAC CS/CJ/CP-series PLCs. The
CompoWay/F communications protocol is used. CompoWay/F is a generic
serial communications protocol from OMRON. An RS-485 interface is used at
the G3PW.
Communications
Specifications
Note
CompoWay/F
CompoWay/F is OMRON's standard communications format for general
serial communications.
It uses commands compliant with the well-established FINS used exten-
sively with OMRON Programmable Controllers together with a consistent
frame format to facilitate communications between more than one compo-
nent and between personal computers and components.
FINS (Factory Interface Network Service)
The FINS protocol provides message communications between control-
lers in OMRON FA networks.
6-1-2
Communications Settings
This section describes the communications settings for the G3PW.
Transmission path connections
Multipoint
Communications method
RS-485 (2-wire, half-duplex)
Sync method
Stop-start sync
Baud rate
9.6, 19.2, 38.4 or 57.6 kbit/s
Transmission code
ASCII
Data length
7 or 8 bits
Stop bits
1 or 2 bits
Error detection
Vertical parity: None, even, or odd
Flow control
None
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......