40
Procedures for Operation and Setting Parameters
Section 4-5
4-5
Procedures for Operation and Setting Parameters
Operating Procedure
Installation and Wiring
Turning ON the Power
*
When the power is turned ON, output will start immediately.
Be careful not to allow large values to be input for current or
voltage signal until the parameter settings have been
completed.
*
If the power is turned ON with no load connected, an SSR
short-circuit (E10) alarm will occur but you will still be able to
set the parameters.
*
The default for the main setting is 4 to 20 mA or 1 to 5 V. The
output mode is for an output proportional to phase angle of the
input (the same mode as the G3PX).
Parameter Settings in the Initial Setting Level
Press the LVL Key for at least 2 s to move to the initial setting
level. Then set the following parameters in order, using the
parameter setting procedure.
•
Settings related to I/O mode
•
Settings related to auxiliary input functions
•
Settings related to alarms
After the parameter settings have been completed, press the LVL
Key for at least 2 s to return to the monitor level.
Parameter Settings in the Adjustment Level
Use the following procedure to set the parameters in the
adjustment level as needed.
Press the LVL Key to move to the adjustment level.
Set the parameters in the adjustment level (such as the Soft-start
Up Time and the Output Upper Limit).
After the parameter settings have been completed, press the LVL
Key to return to the monitor level.
Actual Operation
Summary of Contents for G3PW
Page 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Page 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Page 3: ...iv...
Page 15: ...xvi...
Page 49: ...34 Wiring for Specific Applications Section 3 4...
Page 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Page 77: ...62 Heater Burnout Detection Section 5 9...
Page 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Page 117: ...102 Index...
Page 119: ......