background image

198

Solid State Relays 

G3NH

Solid State Relays

G3NH

Refer to Warranty and Application Considerations  (page 1), Safety 
Precautions
 (page 4), and Technical and Safety Information (page 6).

Switching 75 to 150 A at 240 to 440 VAC

• Easy-to-mount monoblock construction incorporating heat sink.

• Replaceable power cartridge.

• Built-in operation indicator and varistor.

• A series of high-voltage (440 V) models available.

Model Number Structure

Model Number Legend

1. Basic Model Name

G3NH:

Solid State Relay

2. Rated Load Power Supply Voltage

2:

200 VAC

4:

400 VAC

3. Rated Load Current

075:

75 A

150:

150 A

4. Terminal Type

B:

Screw terminals

5. Zero Cross Function

Blank:

Equipped with zero cross function

Ordering Information

List of Models

The built-in Thyristor Modules can be replaced. Refer to the table on page 200 for the model number.

Note: When ordering, specify the rated input voltage.

1

2 3 4 5

G3NH-

@@@@

Isolation

Zero cross 

function

Indicator

Rated output load

Rated input voltage

Model

Photocoupler

Yes

Yes

75 A at 100 to 240 VAC

5 to 24 VDC

100 to 240 VAC

G3NH-2075B

75 A at 180 to 440 VAC

G3NH-4075B

150 A at 100 to 240 VAC

G3NH-2150B

150 A at 180 to 440 VAC

G3NH-4150B

Summary of Contents for G3NH

Page 1: ...State Relay 2 Rated Load Power Supply Voltage 2 200 VAC 4 400 VAC 3 Rated Load Current 075 75 A 150 150 A 4 Terminal Type B Screw terminals 5 Zero Cross Function Blank Equipped with zero cross function Ordering Information List of Models The built in Thyristor Modules can be replaced Refer to the table on page 200 for the model number Note When ordering specify the rated input voltage 1 2 3 4 5 G3...

Page 2: ...0 to 484 VAC G3NH 2150B 100 to 240 VAC 75 to 264 VAC 1 to 150 A 1 800 A 60 Hz 1 cycle G3NH 4150B 180 to 440 VAC 150 to 484 VAC Item G3NH 2075B G3NH 4075B G3NH 2150B G3NH 4150B Operate time 1 2 of load power source cycle 1 ms max DC input 3 2 of load power source cycle 1 ms max AC input Release time 1 2 of load power source cycle 1 ms max DC input 3 2 of load power source cycle 1 ms max AC input Ou...

Page 3: ...0 20 30 0 20 30 50 37 25 60 0 G3NH 150B G3NH 075B Vertical mounting Horizontal mounting Vertical mounting Horizontal mounting Ambient temperature C Load current A Inrush current A Peak Energized time ms G3NH 75 to 264 VAC Input current mA Input voltage V Input current mA Input voltage V Input impedance kΩ G3NH 4 to 30 VDC Input current Impedance Input current Impedance Input impedance kΩ Name Appl...

Page 4: ...p clean the jointing surfaces of the heat sink and thyristor module and apply the new grease supplied as an accessory to the jointing surfaces Secure the thyristor module to the heat sink with the two screws D and tighten each screw to a torque of 2 45 to 2 94 N m 7 Connect the thyristor module to the PWB with the socket The socket may be inserted in either direction Assemble the Base Assembly wit...

Page 5: ...eat sink will rise by approximately 50 C with a rated current flow through the G3NH The G3NH will rise the ambient temperature When mounting the G3NH inside a panel install a fan for proper ventilation When closely mounting the G3NH Solid State Relays side by side reduce the load current 30 lower than the specified value shown in the load current vs ambient temperature graph Take proper measures s...

Reviews: