Resetting Lockout
When the cause of the lockout is removed, the lockout condition can be released by using either of the
following methods.
•Cycle the power back ON
•Reset input (except for lockout due to a communication error or a wiring error)
For manual reset, apply 9 to 24V to the reset input line for 100ms or longer, and then open the switch
to apply a 0 to 1.5V signal or open circuit (pin 4/yellow).
For auto reset, set the reset line open or to 0 to 1.5V for 100ms or longer, and then apply 9 to 24V
again (pin 4/yellow).
ON
OFF
ON
OFF
Toff
/Blocked
Unblocked
Blocked
Unblocked
Auxiliary output 1
Safety output
Toff
x2 or less
Ton
Toff x2 or less