5-4-3-10. Extending Cable Length with Commercially Available Cable
When you need to use a cable that is not specified by OMRON, use a cable that satisfies the following
specifications.
1. Emitter: 5-wire Receiver: 8-wire
2. 0.3 mm
2
or larger, conductor resistance 0.058 ohms/m max.
3. Mute A and Mute B lines, and 24V/0V and 0V/24V lines must be used as twisted-pair lines.
Do not use cables in the same conduit as high voltage or electric power lines.
Emitter cable (Gray)
Receiver cable (Black)
Length
F39-JGR3K-MS-L
F39-JGR3K-MS-D
0.3 m
Notch