Setting with DIP Switch
E
3-2. DIP Switch
Make sure to test the operation of the F3SG-R after setting with DIP Switch to verify that the
F3SG-R operates as intended. Make sure to stop the machine until the test is complete.
Unintended settings may cause a person to go undetected, resulting in serious injury or death.
F3SG-RA series has DIP Switches to configure functions. Configure functions with the DIP Switches before
installing F3SG-RA in your site. To set DIP Switches, turn the power of the F3SG-RA off and open the cover
as shown below. When the setting the DIP Switch is complete, close the cover and turn the power of the
F3SG-RA on.
Cascaded sensors is operated based on the DIP Switches setting of the primary sensor. The DIP Switch
setting of a secondary sensor does not affect the operation.
When attaching the cover, tightly fasten the screws (M2.5, recommended torque: 0.35N.m). Failure to do so may cause the cover
to come loose, leading to deterioration of the protective functions.
The Spatter Protection Cover (F39-HGA, sold separately) extends over the DIP Switch cover of the F3SG-RA. Be sure to use the
Spatter Protection Cover only after all required settings are made to the DIP Switch.
For F3SG-RA series, the following functional settings are available by DIP Switches and Push Switch.
Operate the DIP Switch before turning the power of the F3SG-RA on.
If the DIP Switch is operated during operation of the F3SG-RA, the F3SG-RA transitions to lockout.
A change of the DIP Switch setting is activated upon power-on or lockout reset.
Note that do not use any tool which may damage F3SG-RA’s body when operating the DIP Switch.
For lockout reset function, see
F3SG-RA Series
X
F3SG-RE Series
Receiver
Position
Function
Emitter
Position
Function
1
Scan Code
1
Scan Code
2
External Device Monitoring (EDM)
2
Operating Range Selection
3
Interlock/Pre-Reset
3
4
4
External Test
5
Fixed Blanking/Floating Blanking
6
7
PNP/NPN Selection
8
DIP Switch/Configuration Tool Selection
Receiver
Emitter
Factory Default Setting
Push Switch
Communication Port
1
O
N
2
3
4
1
O
N
2
3
4
5
6
7
8
1
O
N
2
3
4
5
6
7
8
Screw(M2.5)
DIP Switch
(Cover is closed)
Summary of Contents for F3SG-RA
Page 16: ...xiv Introduction F3SG R User s Manual...
Page 24: ...xxii Introduction F3SG R User s Manual...
Page 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Page 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Page 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Page 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...