
176
Ch
apt
e
r
3
Co
nne
ction
t
o SD Ma
nage
r 3
F3SG-SR/PG
User’s Manual
Setting with Intelligent Tap
3-8. Connection to SD Manager 3
Follow the steps below to connect to the SD Manager 3.
To edit backup/restoration data in the Intelligent Tap
1. Connect the Intelligent Tap and computer via a USB cable. Make sure that the DIP Switch Position
1 is set at ON (Lock) and DIP Switch Position 2 at OFF (DIP Switch Disabled). The Intelligent Tap
can run by USB power supply with no external power supply connected.
2. Load the backup/restoration data from the Intelligent Tap, then edit the data with the SD Manager 3,
and write the data to the Intelligent Tap.
3. When the write is complete, unplug the USB cable from the Intelligent Tap.
• Make sure that the DIP Switch Position 1 is set at ON (Lock) before connecting to F3SG-SR/PG and turning on power.
If the DIP Switch Position 1 is set at OFF (Unlock), the Backup is performed and the edited setup data may be
overwritten by the sensor setup data in the connected unit.
• Even when the DIP Switch Position 1 is set at ON (Lock), you can edit the configuration by the SD Manager 3.
To edit F3SG-SR/PG setup data
1. Connect the Intelligent Tap to the F3SG-SR/PG and set the F3SG-SR/PG to the state where the
backup has been performed. Make sure that the DIP Switch Position 1 is set at ON (Lock) and DIP
Switch Position 2 at OFF (DIP Switch Disabled).
2. Connect the Intelligent Tap and computer via a USB cable with the F3SG-SR/PG and the Intelligent
Tap powered.
3. Load the setup parameters, then edit and write them. The setup parameters are written to both
F3SG-SR/PG and Intelligent Tap.
4. Before restarting, make sure that the DIP Switch Position 1 is set at ON (Lock) and DIP Switch
Position 2 at OFF (DIP Switch Disabled), or that the Intelligent Tap is unplugged from the F3SG-SR/
PG.
If the DIP Switch Position 2 is set at ON (DIP Switch Enabled) and if the restoration is performed, settings of interlock,
blanking, and Operating Range Selection will be overwritten by the settings of the DIP switch.
Summary of Contents for F3SG-PG Series
Page 18: ...xvi Introduction F3SG SR PG User s Manual...
Page 30: ...xxviii Introduction F3SG SR PG User s Manual...
Page 74: ...44 Chapter 1 List of Models F3SG SR PG User s Manual Overview and Specifications...
Page 180: ...150 Chapter 2 IO Link F3SG SR PG User s Manual System Operation and Functions...
Page 438: ...408 Chapter 7 Maintenance Checklists F3SG SR PG User s Manual Checklists...