2-14-2. Override at Normal Operation
You can enable the Override function under the normal operation.
Override start conditions under normal operation
If all of the following conditions are satisfied, the OVERRIDE state is enabled.
The F3SG-SR does not enter the OVERRIDE state when the sensor is in LOCKOUT state.
Under standard muting mode
1. Either muting input A or B detects a workpiece. (One or more muting sensors are turned ON by a
workpiece)
2. The F3SG-SR/PG is blocked and the safety outputs are in the OFF state.
3. An input signal of a special sequence is entered three times to the RESET line when the conditions
No. 1 and 2 above are satisfied. The signal must be entered within a range from 0.1 s to the override
input time limit T1 (1 s)(can be changed). (See the timing chart below.)
Under position detection muting mode
1. Either muting input A or B detects a mutable position. (Either muting input A is ON or muting input B
is OFF)
2. The F3SG-SR/PG is blocked and the output is OFF.
3. Under the state of 1 and 2, provide a special sequence to the reset input three (3) times. The signal
must be entered within a range from 0.1 s to the override input time limit T1 (1 s)(can be changed).
(See the timing chart below.)
Under exit-only muting mode
1. Muting sequence error occurred
2. The F3SG-SR/PG is blocked and the output is OFF.
3. Under the state of 1 and 2, a special sequence is entered to the reset input three (3) times. The
signal must be entered within a range from 0.1 s to the override input time limit T1 (1 s)(can be
changed). (See the timing chart below.)
Override end conditions under normal operation
When any of the following conditions is satisfied, the OVERRIDE state is released.
The OVERRIDE state can be also released when the F3SG-SR enters the LOCKOUT state.
Under standard muting mode
1. A period of 600 s (configurable) passes in the OVERRIDE state
2. All muting inputs are turned OFF.
3. The following signal to cancel the OVERRIDE state is entered:
• When the external device monitoring function is enabled, the RESET line is turned ON. (PNP:
Connected to Vs-3 V~Vs; NPN: Connected to 0 V~3 V)
• When the external device monitoring function is disabled, the RESET line is turned OFF.
Under position detection muting mode
1. A period of 600 s (configurable) passes in the OVERRIDE state
2. When muting input A is OFF and muting input B is ON
3. The following signal to cancel the OVERRIDE state is entered:
• When the external device monitoring function is enabled, the RESET line is turned ON. (PNP:
Connected to Vs-3 V~Vs; NPN: Connected to 0 V~3 V)
• When the external device monitoring function is disabled, the RESET line is turned OFF.
Summary of Contents for F3SG-PG Series
Page 18: ...xvi Introduction F3SG SR PG User s Manual...
Page 30: ...xxviii Introduction F3SG SR PG User s Manual...
Page 74: ...44 Chapter 1 List of Models F3SG SR PG User s Manual Overview and Specifications...
Page 180: ...150 Chapter 2 IO Link F3SG SR PG User s Manual System Operation and Functions...
Page 438: ...408 Chapter 7 Maintenance Checklists F3SG SR PG User s Manual Checklists...