The Environment-resistive Slave Units are designed to be easily connected
with M12 connectors that lock by turning them 1/8 of a turn for less wiring.
5-2-1
Mounting in Control Panels
Use screws to mount a Waterproof Terminal in a control panel. These Termi-
nals cannot be mounted on a DIN Track.
Drill the mounting holes in the control panel according to the dimensions
shown in the dimensions diagrams and secure the Terminal with M5 screws.
The appropriate tightening torque is 1.47 to 1.96 N
⋅
m.
Installation Direction
The Terminal can be mounted in any direction. Any one of the following 6
directions is acceptable.
5-2-2
Environment-resistive Terminals with 16 Transistor Inputs (IP67)
ERT1-HD16CH-1
Input Specifications
2
Power or Load Short-circuit Detection Flags for Terminal Block 2
07
06
05
04
03
02
01
00
3
Power or Load Short-circuit Detection Flags for Terminal Block 2
15
14
13
12
11
10
09
08
4
Disconnection Flags for Terminal Block 1
07
06
05
04
03
02
01
00
5
Disconnection Flags for Terminal Block 1
15
14
13
12
11
10
09
08
6
Disconnection Flags for Terminal Block 2
07
06
05
04
03
02
01
00
7
Disconnection Flags for Terminal Block 2
15
14
13
12
11
10
09
08
Byte
offset
Data
Bit 07
06
05
04
03
02
01
00
Item
Specifications
Input points
16 points
Internal I/O common
PNP
ON voltage
15 V DC min. (between each input terminal and 0 V)
OFF voltage
5 V DC max. (between each input terminal and 0 V)
OFF current
1.0 mA max.
Input current
6.0 mA max. at 24 V DC
3.0 mA max. at 17 V DC
ON delay time
1.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits per
common
16 inputs/common
Isolation method
Photocoupler
Input indicators
LEDs (yellow)
Power supply short-circuit
protection
Operates at 50 mA/point min.
Disconnection detection
Operates at 0.2 mA/point max.
Summary of Contents for ERT1 Series
Page 1: ...OPERATION MANUAL Cat No W481 E1 02 EtherNet IP Slave Units ERT1 Series...
Page 2: ......
Page 3: ...ERT1 Series EtherNet IP Slave Units Operation Manual Revised November 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 14: ...xiv...
Page 58: ...38 Recommended Network Devices Section 2 2...
Page 62: ...42 Basic Specifications of Slave Units Section 3 1...
Page 78: ...58 Screw less Clamp Terminals Section 4 2...
Page 92: ...72 Environment resistive Slave Units Section 5 2...
Page 102: ...82 Maintenance and Replacement Section 7 3...
Page 106: ...86 Revision History...
Page 107: ......