7. EQ100 Settings
7-42
Control Value Setting
7.5.5.
■
Function
Specify the upper and lower threshold values for each channel collected by EQ100. In addition,
specify the number of times over the threshold values to evaluate an occurrence of monitoring
alarm.
If a measured data exceeds the setting, an email is sent ("7.5.8. Destination Setting") or output
is made to a general-purpose output ("7.5.9. Output Terminal Setting").
■
Control Value Setting
1) In the setting menu, click [Control Value Setting].
2) Click the [Edit] button of the channel you want to configure.
3) In the [Control Value Setting] dialog box, enter the details.
Setting Item
Description
Upper Limit check box
Select this check box if you want to enable the upper limit
control value.
Upper Limit
Specify the upper limit control value.
Lower Limit check box
Select this check box if you want to enable the lower limit
control value.
Lower Limit
Specify the lower limit control value.
Count
Specify the number of times over the control values to occur a
monitoring alarm.
<Selection> 1 to 8 times
Output Terminal
Set an EQ100 general-purpose output terminal number. If
"None" is set, no output is made to the output terminals.
To make an output to an output terminal, you must configure
the output terminal setting in "7.5.9.Output Terminal Setting”.
for the selected output terminal number.
<Selection> None/1/2/3/4
4) Click [OK].