Power supply voltage 

100 to 240 VAC, 50/60 Hz or 

 

24 VAC, 50/60 Hz/24 VDC

Operating voltage range 

85 to 110% of the rated voltage

Power consumption 

Approx. 12 VA (100 to 240 VAC)

 

Approx. 8.5 VA (24 VAC)/5.5 W (24 VDC)

Indication accuracy 

Thermocouple: 

(Ambient temperature: 23°C)  (±0.1 % of indication value or ±1°C,
 

whichever is greater) ±1 digit max. 

 

Platinum resistance thermometer: 

 

(±0.1 % of indication value or ±0.5°C, 

 

whichever is greater) ±1 digit max.

 

Analog input: ±0.1 % FS ±1 digit max.

Event input 

Output current: approx. 7 mA per contact.

Contact input 

ON:1 k

Ω

 max., OFF: 100 k

Ω

 min.

No-contact input 

ON: residual voltage 1.5 V max.,

 

OFF: leakage current 0.1 mA max.

Control output 1 and 2 

Relay output: SPST-NO,

 

250 VAC, 5 A (resistive load)

 

Electrical life of relay: 100,000 operations

 Control 

Output 

Unit

Control method 

ON/OFF or 2-PID control

Auxiliary outputs 

Relay outputs: SPST-NO,250 VAC, 3 A 

 (resistive 

load), 

 

Electrical life of  relay: 100,000 operations

Ambient temperature 

–10 to 55°C

 

(With no condensation or icing)

Ambient humidity 

25 to 85%

Storage temperature 

–25 to 65°C

 

(With no condensation or icing)

Altitude Max. 

2,000 

m

Recommended fuse 

T2A, 250 VAC, time-lag,

 low-breaking 

capacity

Weight 

Approx. 310 g (main unit only)

Degree of protection 

Front panel: IP66

 

Rear case: IP20, Terminal section: IP00

Installation environment 

Installation category II, pollution

 

degree 2 (as per IEC61010-1)

Memory protection 

Non-volatile memory

 

(Number of write operations: 1,000,000 

 

at an ambient temperature of 25°C) 

Input 

Position proportional potentiometer input,

 

Remote SP input

Transfer output 

4 to 20 mA DC,  Load: 600 

Ω

 max.                           

Specifications

Precautions for Safe Use

Observe the following precautions to prevent failure to operate, malfunctions, or undesirable effects on product 
performance and functions. Problems may occasionally occur. Do not handle the Controller in ways that exceed 
product specifications. 
(1)   This product is designed for indoor use only. Do not use or store the product in any of the following places. 
 

   

• Places directly subject to heat radiated from heating equipment. 

 

   

• Places subject to splashing liquid or oil atmosphere. 

 

   

• Places subject to direct sunlight. 

 

   

• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). 

 

   

• Places subject to intense temperature change. 

 

   

• Places subject to icing and condensation. 

 

   

• Places subject to vibration and large shocks.

(2)   Use/store within the rated temperature and humidity ranges.
 

  Provide forced-cooling if required.

(3)   To allow heat to escape, do not block the area around the product.
 

  Do not block the ventilation holes on the product.

(4)   Be sure to wire properly with correct polarity of terminals.
(5)   Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires to the 

terminal block, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to cross- sectional 
area of 0.205 to 2.081 mm

2

). (The stripping length is 5 to 6 mm.) Up to two wires of same size and type, or two 

crimped terminals can be inserted into a single terminal.

(6)   Do not wire the terminals which are not used.
(7)   Allow as much space as possible between the controller and devices that generate a powerful high- frequency 

or surge.

 

  Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring 

with the power lines when you are wiring to the terminals.

(8)   Use this product within the rated load and power supply.
(9)   Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay 

contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.

(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before 

starting actual control operations to ensure the correct temperature display. 

(11) A switch or circuit breaker should be provided close to this unit.
 

  The switch or circuit breaker should be within easy reach of the operator, and must be marked as a 

disconnecting means for this unit.

(12) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply 

shock to the terminals or electronic components. When inserting the interior of the product, do not allow the 
electronic components to touch the case. 

(13) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol. 
(14) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after 

power ON.

(15) The output may turn OFF when shifting to certain levels. Take this into consideration when performing control.
(16) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when 
 

  frequently overwriting data during communications or other operations.

(17) The product's Setup Tool port and Infrared communication port are internally connected in models. Stop 

transmission from Infrared communication port before using the Setup Tool port.

(18)   Read the information provided in the catalog and manual and be sure you understand it before attaching a Control 

Output Unit. 

(19)  Always use suitable tools to dismantle the product for disposal. 
(20)  Do not continue to use the product if the front surface peels or becomes cracked. 

E5AN-HT

2153002-0A

Instruction Manual

OMRON CORPORATION

 ©All Rights Reserved

Suitability for Use

CAUTION

AHT1

EN

Safety Precautions

CAUTION

Warning Symbols

Digital Controller

Thank you for purchasing the OMRON E5AN-HT Digital 
Controller.  This manual describes the functions, performance, 
and application methods needed for optimum use of 
the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with   

a knowledge of electrical systems.

• Before using the product, thoroughly read and understand 

this manual to ensure correct use.

• Keep this manual in a safe location so that it is available for 

reference whenever required.

For detailed operating instructions, refer to the 

E5CN-HT/E5AN-HT/E5EN-HT 

Digital Controllers User's Manual 

(Cat. No. H169).

Significance of WARNINGs and CAUTIONs

Indicates a potentially hazardous situation which, if 
not avoided, is likely to result in minor or moderate 
injury or property damage. Read this manual 
carefully before using the product.

Do not touch the terminals while power is being supplied. 
Doing so may occasionally result in minor injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to 
enter the product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from 
explosion may occasionally occur. 
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric 
shock, fire, or malfunction may occasionally occur. 

CAUTION - Risk of Fire and Electric Shock

a) This product is UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure that 

does not allow fire to escape externally.

b) More than one disconnect switch may be required to de-energize the equipment before servicing. 
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always 
consider the application conditions and use the output relays within their rated load and electrical life expectancy. 
The life expectancy of output relays varies considerably with the output load and switching conditions. 
Tighten the terminal screws to between 0.74 and 0.90 N•m. Loose screws may occasionally result in fire. 
Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, 
unexpected operation may occasionally result in property damage or accidents. 
A malfunction in the  Digital Controller may occasionally make control operations impossible or prevent 
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital 
Controller, take appropriate safety measures, such as installing a monitoring device on a separate line. 

OMRON shall not be responsible for conformity with any standards, codes, or regulations that 

apply to the combination of the products in the customer's application or use of the product.

Take all necessary steps to determine the suitability of the product for the systems, machines, 

and equipment with which it will be used.

Know and observe all prohibitions of use applicable to this product.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE 
OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN 
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY 
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT 
OR SYSTEM.

See also Product catalog for Warranty and Limitation of Liability.

Dimensions

Installation

Wiring

• Solderless terminal size: M3.5

• Terminal cover:

(Sold Separately) (Model: E53-COV16)

• USB-Serial Conversion Cable 

(Sold Separately) (E58-CIFQ1)

In the pack:
 • Main unit
 • Watertight packing
 • Two mounting brackets
 • Instruction manual

 • Terminal cover
    (Provided only for models 

    with "-500" suffix.)

Individual mounting (mm)

Mounting the output unit

• Insert the main unit through the mounting hole in the panel (1-8 mm 

thickness). Insert the mounting brackets (supplied) into the fixing 
slots located on the top and bottom of the rear case.

• Alternately tighten the top and bottom screws on the mounting 

fixtures applying equal pressure a little at a time until the rachet 
rotates freely.

• When more than one machine is installed, make sure that the 

ambient temperature does not exceed the specified limit.

 [OUT]
  E53-RN
  E53-QN
  E53-Q3
  E53-Q4
  E53-C3N
  E53-C3DN
  E53-V34N
  E53-V35N

Output placement is not required on the E5AN-HTPRR

@@

When waterproofing is 
required, fit watertight 
packing on the backside 
of front panel. 

(Sold Separately) (model E58-CIFIR)

• USB-Infrared Conversion Cable

Watertight

packing

Connections

(The applicability of the electric terminals varies with the type of machine.)

•  A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is output to the output to which the alarm 1 function is assigned.
•  The voltage output (control output) is not electrically insulated from the internal wiring. When using a grounded thermocouple thermometer, one or the other of the control 

output terminals must not be grounded. (If both terminals are grounded, measurements will be unreliable due to sneak current.) 

•  The last character of the lot number “R” indicates that reinforced insulation is provided between input power supply, relay outputs, and between other terminals. 

The E5

@

N-HT is set 

for a K thermocouple 
(input type of 5) by 
default. If a different 
sensor is used, an 
input error (

s.err

will occur. Check the 
setting of the Input 
Type parameter.

OUT1

OUT2

Mounting 

bracket

Dimensions (mm)

Terminal

cover

* The main unit can be removed for maintenance without disconnecting the terminal  wiring.

* Do not remove the terminal block. Doing so may result in failure or malfunction.

* A Setup Tool port is provided on the bottom of the product. Use this port to connect a personal computer to 

the product when using the Setup Tool. E58-CIFQ1 USB-Serial Conversion Cable is required to connect the 

personal  computer to the product. (Do not use the product with the USB-Serial Conversion Cable left permanently 

connected.)

Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods. 

• 100 to 240 VAC
• 24 VAC/VDC (no polarity)

CT2

Potentiometer

Control Output Unit

Control output 1, 2

Event Inputs

Communications

  4-20 mA DC

 max.)

(Load: 600

Ω

4-20 mA DC

-

+

1

2

3

4

5

14

15

6

7

8

9

10

16

17

18

19

23

24

25

26

27

28

29

30

20

CT1

CT2

EV1

EV2

W

C

O

-

+

21

22

13

DO NOT
USE

+

+

B

+

V

mA

B

A

DO NOT
USE

DO NOT
USE

DO NOT
USE

14

15

16

DO NOT
USE

DO NOT
USE

DO NOT
USE

11

12

RS-232C

RS-485

RS-422

SD

11

RD

12

SG

13

RDB

11

RDA

12

SG

13

SDB

21

SDA

22

B(+)

11

A(

)

12

13

B(+)

21

A(

)

22

21

22

25

26

27

28

EV4

EV3

21

22

23

24

29

30

DO NOT 
USE

+

+

DO NOT USE

DO NOT USE

DO NOT USE

Relay output

250 VAC, 5A

(resistive load)

Control output 1, 2

Auxiliary output 

1, 2, 3

250 VAC, 3 A 

(resistive load)

Relay outputs

Input power 
supply

Control output  2

Auxiliary output  1

Auxiliary output  2

Control output  1

Remote SP input

Transfer output

Auxiliary 

output 3

Names of parts on front panel

Operation indicators

• SUB1: Auxiliary output 1 indicator
  Lit when the function assigned to auxiliary 

output 1 is ON. 

• SUB2: Auxiliary output 2 indicator
  Lit when the function assigned to auxiliary 

output 2 is ON.

• SUB3: Auxiliary output 3 indicator
  Lit when the function assigned to auxiliary 

output 3 is ON.

• HA: Heater burnout alarm/Heater short 

alarm/Heater overcurrent alarm indicator
Lit when a heater burnout alarm,heater short 

alarm, or heater overcurrent alarm has 

occurred. 

• Mode key

Press this key to change 
the contents of the display.
Press this key for 1 s or 
longer for reverse scroll.

• °C / °F : Temperature unit 

The temperature unit is displayed 

when the displayed value is a 

temperature.
When this parameter is set to “°C”,

C

” is displayed, and when set to 

“°F”, “

F

” is displayed.

•            : Protection indicator

Lit when Setting Change Protect is 

ON (disables the Up and Down Keys). 

• MANU: Manual output indicator

Lit when the Auto/Manual Mode is set 

to Manual Mode. 

•  Function Key/Run Reset Key 

Press this function key 
to  operate the function 
set with the PF Setting. 

• Level key

Use this key to change levels:

• Press the 

O

 key and the

M

 key together for at least 

3 seconds to switch to 
protect level. 

• Up and Down keys

Use the keys to change the values displayed on 

the No.2 display.

Each press of 

U

 key increments or advances the 

values displayed on the No.2 display.
Each press of 

D

 key decrements or returns the 

values displayed on the No.2 display.

• Ir: Infrared Communications Enabled Indication

Lit when communications are enabled. Not lit when
communications are disabled. 

• Infrared Communications Receiver

Used when using an infrared cable. 

• No.1 display

Process value or set data symbol

• No.2 display

Set point, set data read-out value or changed 

input value 

• No. 3 display

Program number, segment number, etc. 

• OUT1: Control output 1 indicator

Lit when control output 1 is ON 

and not lit when it's OFF.

For a current output, lit except 

for a 0% output. 

• OUT2: Control output 2 indicator

Lit when control output 2 is ON 

and not lit when it's OFF.

For a current output, lit except 

for a 0% output. 

• CMW: communications writing 

enable/disable indicator
Lit when communications writing 

is “enabled” and is out when it is 

“disabled”.

•  RSP: Lit during remote SP Mode. 

Conformance to EN/IEC Standards

This is a class A product. 
In residential areas it may cause radio 
interference, in which case the user may 
be required to take adequate measures 
to reduce interference.

Conformance to Safety Standards

Reinforced insulation is 
provided between input power 
supply, relay outputs, and 
between other terminals.

• WAIT: Lit while the program is in wait status. 

•     : Shows the direction of change in the SP. 

•  FSP: Lit during Constant-value SP Mode. 

•  RST: Lit while the program is being reset. 
•  HOLD: Lit while the program is in hold status. 

*1

*1

*1

Alarms

Operation menu

Operation stopped.
(Control/alarm are both stopped.)

*5

Initial Setting Level

Protect Level

The setting data for the E5AN-HTAA2HB is shown here as an example. 

Check the wiring before turning ON the power supply. 

Adjustment Level

RSP absolute value upper limit

RSP absolute value lower limit

Vary with "L", "H" values

Vary with "L", "H" values

Vary with "L", "H" values

X

ON
OFF

SP

X

ON
OFF

SP

ON
OFF

SP

X

X

ON
OFF

SP

L H

ON
OFF

SP

X

ON
OFF

SP

X

ON
OFF

SP

X

ON
OFF

0

ON
OFF

X

0

X

ON
OFF

0

X

ON
OFF

0

ON
OFF

X

0

X

ON
OFF

0

L H

ON
OFF

SP

L

H

ON
OFF

SP

SP

X

ON
OFF

SP

ON
OFF

X

ON
OFF

X

0

14

15

X

ON
OFF

0

X

ON
OFF

0

ON
OFF

X

0

ON
OFF

X

0

ON
OFF

X

0

1

0

2

3

4

5

6

7

8

9

10

11

12

13

Alarm output function

Positive alarm value (X) Negative alarm value (X)

Alarm type

Setting

Output off

Hold 

O

 down

for at least

1 second

Advanced Function 
Setting Level

Operation Level

(The No. 3 display 
has been omitted.) 

PID Setting Level

Moving to the next level is 
possible when the 
password(-169) is input. 

oapt

0

icpt

0

wtpt

off

pfpt

off

Segment No. Monitor

Auto/Manual Switch 

Hold

Advance

Remaining Standby 
Time Monitor

Elapsed Program 
Time Monitor

Program Execution 
Repetition Monitor

25.0

0.0

*6

*6

ct1

0.0

*6

lcr1

0.0

*6

r-r

rst

seg

0

hold

off

adv

off

stbm

0.00

prgt

0.00

rptm

0

prlp

0

*6

*6

*6

*6

*6

*6

Program Number 

prg

0

rsp

0.0

init

off

a-m

*6

*6

*6

*6

*6

*6

*6

l.adj

at

off

*6

*6

hb1

0.0

*6

ins

0.00

insh

0.00

insl

0.00

p

8.0

i

233.0

*6

d

40.0

*6

*6

*6

*6

*6

*6

hys

1.0

chys

1.0

ol-h

105.0

ol-l

-5.0

c-db

0.0

of-r

50.0

*6

c-sc

1.00

lcr1

0.0

*6

orl

0.0

*6

sqrp

0.0

Standby Time 

stb

0.00

*6

oc1

50.0

hs1

50.0

irda

off

*6

ct1

0.0

spmd

psp

*6

Constant SP 

fsp

0.0

*6

wt-b

off

d.pid

1

*6

*6

*6

*6

*6

*6

*6

*6

Event Input 1 Assignment 

Event Input 2 Assignment 

Program Time Unit 

Time Setting/Slope Setting 

Slope Time Setting Unit 

Reset Operation 

Operation after Power ON 

Operation at End of Operation 

PV Start 

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

t-u

h-m

pru

m

rtsm

stop

p-on

cont

eset

rst

t-pr

time

pvst

sp

amov

0

in-t

5

in-h

100

in-l

0

dp

0

d-u

c

sl-h

1300.0

sl-l

-200.0

cntl

pid

s-hc

stnd

cp

20

c-cp

20

orev

or-r

alt1

2

alt2

2

tr-t

off

tr-h

100.0

tr-l

0.0

alh1

0.2

alh2

0.2

ev-1

rr-1

ev-2

adv

sqr

off

d.seg

1

d.seg

0

pid

1

al-1

0.0

al1h

0.0

al1l

0.0

al-2

0.0

al2h

0.0

al2l

0.0

al-3

0.0

al3h

0.0

al3l

0

rpt

0

link

end

ts1s

0

on1

0.00

of1

0.00

styp

ramp

sp

0.0

pr

0.0

time

0.00

t525

0

on2

0.00

of2

0.00

s-no

8

d.seg

end

d.seg

7

d.prg

2

d.prg

1

d.prg

0

d.prg

7

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

POWER  ON

Extraction of Square
Root Low-cut Point 

Derivative Time
(Unit: secs)

Dead Band

Manual Reset Value
(Unit: %)

Hysteresis
(Cooling)

MV Upper Limit

MV Lower Limit

Hysteresis
(Heating)

Cooling Coefficient

Wait Band

MV Change Rate Limit

Integral Time
(Unit: secs)

Temperature Input Shift
(Unit:°C or°F)

Upper Limit Temperature 
Input Shift Value
when 2 point input shift
is selected  

Lower Limit Temperature
Input Shift Value
when 2 point input shift  
is selected

Adjustment Level

Proportional Band

Leakage Current 1
Value Monitor 

(Unit: A) 

*7

Heater Burnout
Detection 1

(Unit: A) 

*7

HS Alarm 1

(Unit: A) 

*7

Heater Overcurrent
Detection 1 

(Unit: A) 

*7

SP Mode

AT Execute/Cancel

100%AT Execute 

 

at-2

40%AT Execute 

 

at-1

Heater Current 1
Value Monitor

(Unit: A) 

*7

Adjustment level is for entering set 

values and shift values for control.

Infrared 
Communications 
Usage 

Input Type 

*3

Scaling Upper Limit
 (only when setting analog input)

Scaling Lower Limit 
(only when setting analog input)

Decimal Point 
(only when setting analog input)

Temperature Unit

SP Upper Limit

SP Lower Limit

PID ON/OFF
In ON/OFF control = 

onof

In 2-PID control = 

pid

Standard or Heating/Cooling
Standard control = 

stnd

Heating and cooling control = 

h-c

(Select standard control or heating
and cooling control as required) 

Control Period (Heating)
(Unit: Seconds)

Alarm 2 Type:

Alarm 1 Type:

Control Period (Cooling)
(Unit: Seconds)

°C=

c

°F=

f

(C stands for Celsius, F for Fahrenheit)

Direct/Reverse Operation

In Reverse Operation (Heating) 

=

or-r

In Direct Operation (Cooling)

 =

or-d

*3
*4

*3
*4

Transfer Output Type

Transfer Output Upper Limit

Transfer Output Lower Limit

Initial setting level enables users to specify their 
preferred operating conditions (input type, alarm type, 
control method, etc.)

Extraction of Square Root Enable
(Only when analog input is set)

Alarm 1 Hysteresis

Alarm 2 Hysteresis

Move to Advanced
Function Setting Level

Restricts which settings can be displayed 
or changed, and restricts change by key 
operation.

PF Key Protect

Operation / Adjustment
Protect

Initial Setting / 
Communication

Protect

Setting Change Protect

Password to Move 
to Protect Level

*

5: Operation is stopped when moved to the 

initial setting level. (Control/alarm are 
both stopped.)

*

6: The grayed-out setting items may not 

be displayed according to the models 
and setting.

*

7: This function is supported only by 

models with heater burnout detection.

*

3: Refer to the adjoining tables for details of 

input types and alarm types. 

*

4: Applicable only to models with alarm 

functions.

Operation level should normally 

be used during operations. 

PV/SP

s.err

 is displayed when 

connected sensor is 
different from input type.

Heater Current 1 
Value Monitor

(Unit: A) 

*7

Leakage Current 1 
Value Monitor

(Unit: A) 

*7

Remote SP Monitor

Hold 

O

 and 

M

   

keys down for at 
least 1 seconds

Hold 

O

 and 

M

   

keys down for at 
least 3 seconds

Display PID 
Selection

Parameter
Initialization

Hold 

O

 down for 

at least 3 seconds

Hold 

O

 down for 

at least 1 second

Only the value set to the “

ins

: Temperature Input Shift” parameter is applied to the entire 

temperature input range. When the process value is 200 °C, the process value is treated as 
201.2 °C after input shift if the input shift value is set to 1.2 °C.The process value is treated as 
198.8 °C after input shift if the input shift value is set to –1.2 °C.

Run/Reset 
At start of program operation:

run

At end of program operation: 

rst

    : Can be displayed 
      and changed
    : Can be displayed
×  : Display or shifting to 
     another level is not 
     possible. 

Default setting : 0

× : Change to other levels not possible 

Protection function

Operation/Adjustment protection

Setting change protection

Setting changes by key operation are restricted. 

OFF

off

: Setting can be changed by key operation 

ON

on

    : Setting cannot be changed by key operation (“       ” will light.) 

(Protect level settings can all be changed.)

Other functions

    : Change to other levels possible  

*

AT in Adjustment level

Designate "

at-2

: 100% AT execute" or 

"

at-1

: 40%  AT execute" to execute AT and 

"

off

: AT cancel" to cancel AT. 

at

” flashes

“AT cancel”

Also when AT execution ends, the 
display automatically returns to “

off

”.           

at

off

at

at-2

AT (auto-tuning)

“100%AT Execute”

Set value

0

1
2

×

×

×

×

Initial setting

level

Communications 

setting level

Advanced function 

setting level

Initial setting/Communications protection

This protect level restricts movement to the initial setting level, 
communications setting level and advanced function setting level.

OMRON EUROPE B.V.

Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
 Phone 31-2356-81-300
 FAX 31-2356-81-388

OMRON ELECTRONICS LLC

One Commerce Drive Schaumburg, IL 60173-5302 U.S.A   
    Phone 1-847-843-7900
 FAX 1-847-843-7787

OMRON ASIA PACIFIC PTE. LTD.

No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
 Phone 65-6835-3011
 FAX 65-6835-2711

OMRON Corporation

Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN

The following table shows the relationship between settings and 
protect limits related to Operation level and Adjustment level.

Protection function, to prevent unwanted settings, 
restricts the setting items to be used or designates 
if operation of the key is valid or invalid. 

Default setting : 0

     Process value
     PV/SP
     Others

Program Setting Level
Adjustment level
PID Setting Level

Level

Set value

Oper

a

tion

 le
v

e

l

For parameters in the Advanced Function Setting 
Level, PID Setting Level, Monitor/Setting Item 
Level, and Manual Control Level and for other 
information, refer to the 

E5CN-HT/E5AN-HT/E5EN-HT User's Manual 

(Cat. No. H169).
For information on communications, refer to the 

E5CN-HT/E5AN-HT/E5EN-HT Communications  
Manual

 (Cat. No. H170).

Protection can be set for the PF Key operation.    

PF key protection

OFF “

off

”: PF Key enabled.

ON   ”

on

”  : PF Key disabled.

Press 

O

 Key for less than 1 s.

Press 

O

 Key for less than 1 s.

Press 

O

 Key 

for less than 1 s.

Press 

O

 Key 

for less than 
1 s.

Display Program Selection

Program Setting Level

Number of Segments 
Used, 1 to 32 

Display Segment Selection, 

END or 0 to Number of 

Segments − 1

PID Set 
No. 

Alarm 
Value 1 

Alarm 
Upper 
Limit 1 

Alarm 
Lower 
Limit 1 

Alarm 
Value 2 

Alarm 
Upper 
Limit 2 

Alarm 
Lower 
Limit 2 

Alarm 
Value 3 

Alarm 
Upper 
Limit 3 

Alarm 
Lower
Limit 3 

Program 
Repetitions

Program Link 
Destination

Time Signal 1 
Set Segment

Time Signal 1 
ON Time 

Time Signal 1 
OFF Time

Segment 
n Format

Segment 
n SP

Segment 
n Slope

Segment 
n Time

Time Signal 2 
Set Segment 

Time Signal 2 
ON Time

Time Signal 2 
OFF Time

In this level, the SPs and times 
are input for the programs. 

*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for 

different types of alarm. These are indicated by the letter "L" and "H". 

  • The default alarm type is "2"

*2: Error shown only for "Process value / Set point". Not shown for other status. 

When an error has occurred, the No.1 display shows the error code. Take 
necessary measure according to the error code, referring the table bellow.

If the input value exceeds the display limit ( -19999 to 32400), though it is within the control 
range, 

[[[[

will be displayed under  -19999 and        

]]]]

 above 32400. Under these conditions, 

control output and alarm output will operate normally.
For information on the controllable range, refer to the 

E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers 

User's Manual 

(Cat. No. H169).

Turn the power OFF then back ON again. If the 
display remains the same, the controller must be 
repaired. If the display is restored to normal, then 
a probable cause can be external noise affecting 
the control system. Check for external noise.

After the correction of A/D converter error, turn the 
power OFF then back ON again. If the display 
remains the same, the controller must be repaired. 
If the display is restored to normal, then a 
probable cause can be external noise affecting the 
control system. Check for external noise.

No.1 display

Meaning

A/D converter error 

*2

Memory error

Input error

*2

s.err

(S. Err)

e111

(E111)

Action

OFF

Alarm

Control

output

Status at error

OFF

OFF

Operates 

as above the 

upper limit.

OFF

OFF

e333

 (E333)

Input type

Error display (trouble shooting)

 *The default is“5”.

  *

s.err

 will be displayed when a platinum resistance thermometer is mistakenly connected while 

input type is not set for it. To clear the 

s.err

 display, correct the wiring and cycle the power supply.

200.0 to  850.0 (°C)

199.9 to  500.0 (°C)

      0.0 to  100.0 (°C)

199.9 to  500.0 (°C)

      0.0 to  100.0 (°C)

200.0 to 1300.0 (°C)

  

20.0 to  500.0 (°C)

100.0 to  850.0 (°C)

  

20.0 to  400.0 (°C)

200.0 to  400.0 (°C)

199.9 to  400.0 (°C)

200.0 to  600.0 (°C)

100.0 to  850.0 (°C)

200.0 to  400.0 (°C)

199.9 to  400.0 (°C)

200.0 to 1300.0 (°C)

      0.0 to 1700.0 (°C)
      0.0 to 1700.0 (°C)
  100.0 to 1800.0 (°C)
      0.0 to 2300.0 (°C)
      0.0 to 1300.0 (°C)
  

50.00 to 200.00 (°C)

  

50.00 to 200.00 (°C)

  

50.00 to 200.00 (°C)

  

50.00 to 200.00 (°C)

300.0 to 1500.0 (°F)

199.9 to  900.0 (°F)

/      0.0 to  210.0 (°F)

199.9 to  900.0 (°F)

/      0.0 to  210.0 (°F)

300.0 to 2300.0 (°F)

/      0.0 to  900.0 (°F)

100.0 to 1500.0 (°F)

/      0.0 to  750.0 (°F)

300.0 to  700.0 (°F)

199.9 to  700.0 (°F)

300.0 to 1100.0 (°F)

100.0 to 1500.0 (°F)

300.0 to  700.0 (°F)

199.9 to  700.0 (°F)

300.0 to 2300.0 (°F)

/      0.0 to 3000.0 (°F)
/      0.0 to 3000.0 (°F)
/   300.0 to 3200.0 (°F)
/      0.0 to 3200.0 (°F)
/      0.0 to 2300.0 (°F)
/   

50.00 to 200.00 (°F)

/   

50.00 to 200.00 (°F)

/   

50.00 to 200.00 (°F)

/   

50.00 to 200.00 (°F)

K

J

T

E

L

U

N

R

S

B

W

PLII

K

J

T

Pt100

4 to 20mA
0 to 20mA

1 to 5V
0 to 5V

0 to 10V

0
1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23

24

25
26
27
28

29

One of the following ranges is used depending on scaling.

  :

 

19999 to 32400

 

1999.9 to 3240.0

 

199.99 to 324.00

 

19.999 to 32.400

Input type

Platinum
resistance
thermometer

Input

Pt100

JPt100

Thermocouple

Platinum

resistance

thermometer

Current input

Voltage input

Setting

Input setting range

No alarm function

Deviation upper/lower limit
standby sequence ON

Absolute value upper limit

Absolute value lower limit

Absolute value upper limit
standby sequence ON

Absolute value lower limit
standby sequence ON

LBA (only for alarm 1)

Deviation lower limit 
standby sequence ON

Deviation upper limit
standby sequence ON

Deviation upper/lower range

Deviation upper limit

Deviation upper/lower limit

Deviation lower limit

PV change rate alarm

Check the setting of the Input Type parameter, 
check the input wiring, and check for broken or 
shorts in the temperature sensor.  

Auxiliary output  3

6

112

79.2

91 

×

 91

78

2

96 

×

 96

120 m

in

+0.8

 0

+

0

.8

  

0

92

92

Clamps

For other information, refer to the 

User's Manual

 (Cat. No. H169).

For other information, refer to the 

User's Manual

 (Cat. No. H169).