![Omron E5AC Communications Manual Download Page 46](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553046.webp)
2 CompoWay/F Communications Procedures
2 - 14
E5@C Digital Temperature Controllers Communications Manual (H175)
(3) Response Code
•
Normal Completion
•
Error Occurred
This service reads the operating status and error status.
•
Service Request PDU
•
Service Response PDU
(1) Operating Status
(2) Related Information
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Description
1001
Command too long
The command is too long.
2203
Operation error
Non-volatile memory error
2-3-6
Read Controller Status
Operating status
Description
00
Control is being carried out (error has not occurred in setup area 0 and the Controller is
running).
01
Control is not being carried out (state other than above).
MRC
SRC
0
6
0
1
2
2
MRC
SRC
0
6
0
1
2
2
4
2
2
Response
code
Operating
status
Related
informa-
tion
7
6
5
4
3
2
1
0
Heater current hold (CT1)
AD converter error
Heater overcurrent (CT2)
Heater current hold (CT2)
Input error
Heater overcurrent (CT1)
0
Bit position
Potentiometer input error
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......