6 - 7
6 Programless Communications
E5@C Digital Temperature Controllers Communications Manual (H175)
6-2 E5
C Set
u
p
6
6-
2-1 Pro
tocol Setting
6-2
E5
C Setup
The parameters that are used for programless communications are shown with a gray background in
the following diagram. These parameters will be displayed if you set the Protocol Setting parameter to
fins
,
mcp4
, or
fxp4
. (Some of the parameters are always displayed.) The parameters in the commu-
nications setting level are described first, followed by those in the adjustment level.
*
These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
Set the Protocol Setting parameter to
fins
to connect to an OMRON PLC,
mcp4
to connect to a Mit-
subishi Q-series or L-series PLC,
fxp4
to connect to a Mitsubishi FX-series or Keyence KV-series
PLC, and
cmp
to use component communications. Refer to
for lists of the
PLCs that can be connected.
Refer to
for information on component communications.
Communications Setting Level
Display condition: None
*
Selection is possible only for E5
@
C version 2.1 or later.
6-2-1
Protocol Setting
Parameter name
Displayed characters
Setting range
Default
Protocol Setting
psel
cwf
: CompoWay/F
mod
: ModbusRTU
cmp
: Component communications
fins
: Host Link (FINS)
mcp4
: MC protocol (format 4)
fxp4
: Dedicated protocol (format 4)*
cwf
Initial Setting Level
Operation Level
M
M
M
M
M
Protocol Setting
*
Communications
Unit No.
*
Communications
Baud Rate
*
Send Data Wait
Time
*
Highest
Communications
Unit No.
Area
Communications Setting Level
Power ON
M
M
M
M
M
First Address Upper
Word
First Address Lower
Word
Receive Data Wait
Time
Communications
Node Number
Upload Setting 1
M
M
M
M
Upload Setting 2
Download Setting 1
Download Setting 2
Copy
M
M
M
M
Adjustment Level
Display
AT Execute/Cancel
Communications
Writing
*
Work Bit 8 OFF Delay
Adjustment Level
M
M
Communications
Monitor
Press
O
Key for
less than 1 s.
Press
O
Key for
at least 3 s.
Press
O
Key for
at least 1 s.
Press
O
Key for
less than 1 s.
25
0
psel
fins
u-no
0
bps
57.6
sdwt
20
maxu
0
adrh
0
adrl
0
rwat
1000
unit
0
area
0
up 2
2
dn 1
31
dn 2
61
copy
off
up 1
1
l.adj
1234
at
off
cmwt
on
plcm
0
w8of
0
in-t
5
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......