5 E3NW-CCL Hardware Specifications
5 - 6
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
This switch sets the CC-Link baud rate and operating mode.
The following table describes the settings.
Set the same baud rate as is set by the rotary switch on the master station unit.
Precautions for Correct Use
•
The settings of the setting switches are read only once when the power is turned ON.
Changing this setting after the power is turned ON will have no effect until after the next time
the power is turned ON.
•
If these switches are changed after the power is turned ON, the ERR indicator will light.
5-3-2
Setting Switches
Baud Rate/Operating Mode Setting Switch
Switch
Appearance
/Display
Setting
Baud
rate/operating
mode setting
switch
This switch sets the CC-Link baud rate and operating mode.
Switch setting
Baud rate
Operating mode
0
156k
Reduced I/O Mode (Ver.
1 Mode)
1
625k
2
2.5M
3
5M
4
10M
5
156k
Monitor Mode (Ver. 2
Mode)
6
625k
7
2.5M
8
5M
9
10M
An error will occur if the operating mode does not match the CC-Link mode set in
the master station’s CC-Link parameters and the ERR indicator will light up.
Station number setting (x10)
Station number setting (x1)
Baud rate/operating mode setting