3 Basic Application Procedures
3 - 2
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
3-1
Setting Examples and Basic
Procedures
This section describes how to set up a Sensor Communications Unit based on a simple system setting
example.
Connect each of the following slaves to the CC-Link master and configure the settings.
The Unit power supply and I/O power supply are not shown in the above figure. They must be
provided separately.
Reference
The setting example provided here demonstrates the basic settings for the E3NW-CCL Sensor
Communications Unit. If more detailed settings are required for actual operations, refer to the
manual for your CC-Link master.
Or, if you are using any slaves other than the E3NW-CCL in your system configuration, refer to
the manuals for those slaves before setting up the system.
3-1-1
System Setting Example
CC-Link master
Digital I/O slave (16 inputs)
Set the station number to 1. (One station is allocated.)
Digital I/O slave (16 outputs)
Set the station number to 2. (One station is allocated.)
Analog Input Slave (4 inputs)
Set the station number to 3. (Three stations are allocated.)
E3NW-CCL Sensor Communications Unit
Set the station number to 6
(Reduced I/O Mode: Two stations are allocated,
Monitor Mode: Three stations are allocated.)
Up to eight E3NW-DS Units can be connected to one
E3NW-CCL Unit. A maximum of 16 Sensor Amplifier
Units can be connected to the E3NW-CCL, and a
maximum of 10 Sensor Amplifier Units can be
connected to each E3NW-DS. However, a total
maximum of 16 Sensor Amplifier Units can be
connected in one E3NW-CCL system.