68
Editing Parameters
Section 3-1
3-1-9
Safety Output Logic Parameter Groups (Safety Output Logic)
Safety output parameter groups can only be set for the DST1-XD0808SL-1.
Set these parameters using the Safety Logic Wizard.
Note
(1) Turns OFF (0) when one of the errors shown in
occurs.
(2) Safety output parameter groups can be set only for DST1-XD0808SL-1
safety outputs OUT0 to OUT7. For details on DST1-XD0808SL-1 logic
functions, refer to
.
Parameter name
Value
Description
Default
S
Output Condition
Output from network
Uses a safety output terminal as a network output.
The value (safety output) received from the net-
work is directly output.
Output
from net-
work
Logic operations for
safety input logic opera-
tion results and remote
I/O signals (Output from
internal logic)
Uses the output as a safety output terminal logic
output. The logic operation result is output. Set
logic operations for safety input logic operation
results and remote I/O (received from the Master).
Additional output
Uses a safety output terminal as an additional out-
put terminal. Select the data to be output as the
additional output data.
S
Welding Check (EDM)
Feedback
Not Used
EDM feedback is not used.
Not Used
IN4
EDM feedback is used. Select the terminals for
connecting feedback signals from external devices.
IN5
IN6
IN7
S
Additional Output Data
Not Used
This setting is enabled when the safety output con-
dition is set to
additional output
.
Not Used
OUT0
Outputs the same value as OUT0.
OUT0 (NOT)
Outputs the inverse value of OUT0.
OUT2
Outputs the same value as OUT2.
OUT2 (NOT)
Outputs the inverse value of OUT2.
OUT4
Outputs the same value as OUT4.
OUT4 (NOT)
Outputs the inverse value of OUT4.
OUT6
Outputs the same value as OUT6.
OUT6 (NOT)
Outputs the inverse value of OUT6.
Reset Required Indica-
tion
Outputs a 1-Hz pulsing signal to trigger a reset
input.
RUN Status Flag
Outputs the operating mode.
0: Not RUN mode
1: RUN mode
Normal Status Flag
Outputs the status.
0: Error (See note 1.)
1: Normal
S
Off On Delay
0 to 300,000 ms (Unit:
100 ms)
Sets the ON delay time.
0 ms
S
On Off Delay
0 to 300,000 ms (Unit:
100 ms)
Sets the OFF delay time.
0 ms
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...