114
Indicators and Error Processing
Section 7-1
7-1
Indicators and Error Processing
: Lit
: Flashing
: Not lit
MS
NS
LOCK
I/O
PWR
I/O
Description
Probable cause and remedy
Green Red
Green Red
Yellow Green
Yellow Red
−
−
−
Safety I/O communications in
progress (normal status)
−
−
−
−
−
−
RUN status
(DST1-XD0808SL-1 only)
−
−
−
Standard I/O communications or
message communications in
progress (normal status)
−
−
−
The DST1 performing initializa-
tion process or waiting for config-
uration.
−
−
−
−
Waiting for safety or standard
connection
−
−
−
−
Communications timeout
Check the following items and restart the
DST1.
Are lengths of cables (trunk and branch
lines) correct?
Are cables broken or loose?
Are Terminating Resistors connected to
both ends of the trunk line only?
Is noise interference excessive?
−
−
−
−
BusOff status (communications
stopped due to consecutive data
errors)
Node address duplication
Reset the DST1 so that it has a unique
node address, and then restart the DST1.
−
−
−
−
Waiting for completion of node
address duplication check
−
−
−
−
Switch settings are incorrect
Check the node address, and then restart
the DST1.
Input
−
Output
System failure
Check to see if the positive side of the
power supply is in contact with the signal
line.
Replace the DST1 if the system failure
still occurs after turning the power supply
ON again.
−
−
−
−
−
Input/output power is not sup-
plied.
Check the following items.
Are cables broken?
Is the I/O power voltage within specifica-
tions?
−
−
−
−
−
An error occurred in an input/
output circuit.
Check the following items.
• Has a ground fault occurred in the
signal line?
• Is the signal line broken?
• Are there any troubles with the con-
nected device?
• Is the power source (positive side) in
contact with the signal line?
• Has a short-circuit occurred in the
signal line?
• Is the discrepancy time setting suit-
able?
• Is the I/O power supply voltage within
specifications?
• Did an EDM error occur?
Details on the error can be read from the
Network Configurator.
−
−
−
−
−
When dual channels are set: An
error occurred in the other chan-
nel.
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...