F"")"-@*.($%')"+
Section 5-1
$'%
5-1
Error Indicators
The RUN-, ERC-, and ERH-LEDs, at the front panel of the High-speed Counter
Unit, display the following errors.
5-1-1
Errors during initial processing
5-1-2
Errors during normal operation
RUN
ERC
ERH
RUN
ERC
ERH
Error
Probable cause
Remedy
OFF
OFF
ON
Setup error
Incorrect Unit number
Cyclic initial error
Set correct Unit number and turn
ON the power again
OFF
ON
OFF
DM-configuration
error
Invalid DM-setting(s)
Check the Error Code(s) in CIO
(words n+17, n+18), correct the
invalid DM-setting(s) and turn ON
the power again. Refer to 5-2
for more information on error
codes and how to clear them.
Unit error
An error occurred in the
Unit’s EEPROM, RAM or
CPU or a system software
error occurred
Turn OFF and then ON the power
again. If errors reoccurs then
replace the High-speed Counter
Unit
OFF
ON
ON
Unit classification
error
The Unit classification was
set incorrectly
Replace the High-speed Counter
Unit
OFF
OFF
OFF
Watch Dog Timer
time-out error
The Unit’s Watch Dog Timer
has timed out
Turn OFF and then ON the power
again. If errors reoccurs then
replace the High-speed Counter
Unit
RUN
ERC
ERH
Error
Probable cause
Remedy
ON
ON
OFF
Unit error
Invalid operands specified
in IOWR-instruction
Overflow or underflow of
Simple or Linear Counter
Preset error
Unit interrupt FIFO is full
Check the Error Code(s) in CIO
(words n+17, n+18). Apply
appropriate remedy according to the
cause of the error. Refer to 5-2
for more information on error
codes and how to clear them.
ON
OFF
ON
System error
PLC Watch Dog Timer error
Fatal error
Non-fatal error
Cyclic Monitor error
I/O Bus error
Extend the cyclic monitor time or
remove the cause of the fatal or non-
fatal error. If the error reoccurs then
replace the CS1-CPU. Refer to 5-2-6
for more
information.
W902-E2-03.book Seite 142 Donnerstag, 7. Oktober 2004 2:06 14
Summary of Contents for CS1W-CT021
Page 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Page 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Page 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Page 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Page 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Page 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Page 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...