79
What Are Data Links?
Section 5-1
Application Example of Using Offsets
In the following example, the send data from node 1 is split into three parts
and each part is received by a different node, i.e., each of the other nodes
receives only part of the send data from node 1. This enables effective use of
data link memory areas without wasting space. In this way, a type of message
service (i.e., specific data to a specific node) can be achieved through data
links.
5-1-1
Data Link Specifications
Note
1.
In systems that combine Optical Bus Controller Link Units/Boards (model
numbers ending with CLK11) with other Units/Boards, the max. number of
nodes and words are as follows:
Even when the CX-Programmer’s CX-Net is being used as the Program-
ming Device, the maximum number of data link nodes is 32 nodes (node
addresses 1 to 32). The maximum number of data link words/node is
32,000 words when the maximum number of nodes is 32 nodes.
2.
If Controller Link Units are used in duplex operation, the maximum number
of active nodes is equal to the following:
62
−
Number of standby Units
# 1
# 2
# 3
# 4
Send data of node 1
Item
Description
Number of
data link
nodes
62 max., 2 min. (See note 1 and 2.)
Number of
data link
words
Number of send/receive words per node (total of Area 1 and Area 2):
CS:
12,000 max.
CVM1/CV:
8,000 max.
IBM or compatible:
Manual setting:
62,000 max. (See note 1.)
(See note 3.)
Automatic setting: 8,000 max.
Number of send words per node
(total of Area 1 and Area 2): 1,000 max.
Allocation of
data link
areas
Manual
setting
Area 1, 2:
Bit area (IR, CIO, and LR Areas)
Data Memory (DM and EM Areas)
However, Area 1 and Area 2 cannot be set in the same
memory area.
Automatic
setting
Area 1: IR, CIO, or LR Area
Area 2: Data Memory (DM and EM Areas)
Method
Specification
Manual
Optical Bus Units/Boards:
Up to 32 nodes (with node addresses 1 to 32) can be data linked
and the max. number of data link words is 32,000 words/node.
Optical Ring Units/Boards:
Up to 62 nodes (with node addresses 1 to 62) can be data linked
and the max. number of data link words is 62,000 words/node.
Automatic
All Units/Boards:
Up to 32 nodes (with node addresses 1 to 32) can be data linked
and the max. number of data link words is 32,000 words/node.
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...