61
Optical Wiring
Section 3-3
• Do not bend the cable too sharply. The minimum radius for bends is
10 cm.
• To prevent the Optical Fiber Cable from being pulled too forcefully, always
use the cable securing bracket and provide space below the Unit as
shown in the following diagram. Do not exceed the maximum tension for
the cord and cable:
Cord:
0 kg (Do not apply any tension.)
Cable: 5 kg
• Do not place objects on top of the Optical Fiber Cable. The maximum
pressure that can be placed on the cord and cable is as follows:
Cord:
30 kg/10 cm
Cable: 50 kg/10 cm
• Inspect the connector before installing it.
3-3-5
Connecting Optical Fiber Cable to Connectors for GI Cable
A special connector (ST connector) is used to connect the GI Optical Fiber
Cable to the Controller Link Unit.
Connect the GI Optical Fiber Cables to the nodes in order from higher to lower
nodes. (When a ring topography is being used, connect the last node to the
first node, too.)
Observe the following precautions when connecting the Optical Fiber Cables.
• Always turn OFF the PLC power supply before connecting Optical Fiber
Cables.
• Special tools and skills are required to attach Optical Fiber Cables to the
connectors. The cable may disconnect from the connector if the proper
tools and methods are not used during cable assembly.
Connection Procedure
Use the following procedure to connect Optical Fiber Cables to a Unit.
1,2,3...
1.
Attach the mounting bracket to the Unit with the provided screws.
50
60
200
Cord
Cable
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...