76
Section 4
Using th
e Dist
ribut
ed Sen
s
or Unit
E3NW-CRT
User’s Manual
Section 4
Hardware Specifications of the Distributed Sensor Unit
DS-Bus Network Termination Setting Switch
This switch turns the communications terminating resistance ON or OFF on the DS-Bus
network.
Turn ON the DS-Bus termination setting switch for the last Distributed Sensor Unit on the
DS-Bus network. Turn this switch OFF for all other Distributed Sensor Units. This is shown
in the following figure.
Termination setting switch
Sensor Communications Unit
DS-Bus
communications cable
First Sensor Distribution Unit
• Termination setting switch: OFF
Second Sensor Distribution Unit
• Termination setting switch: OFF
nth Sensor Distribution Unit
• “n” is a maximum of 8.
• Termination setting switch: ON
L2
L1
Ln