141
Internode Test
Section 9-3
Method
Input the following at the host computer prompt ($):
$
ping
IP_address(host_name)
The destination is specified by its IP address or host name. If the host name is
used, the host name must be defined in file /etc/hosts.
Note
The PING command is not supported by some host computers.
Application Examples
These examples show sending the PING command to the node at IP address
130.25.36.8. The “$” on the example screen represents the host computer
prompt. User inputs are underlined. Comments are placed after semicolons.
Normal Execution
$
ping 130.25.36.8
; Executes PING command
PING 130.25.36.8: 56 data bytes
64 bytes from 130.25.36.8: icmp_seq=0. time=0.ms
64 bytes from 130.25.36.8: icmp_seq=0. time=0.ms
.
.
.
.
.
.
.
.
.
64 bytes from 130.25.36.8: icmp_seq=0. time=0.ms
←
Enter Ctrl+C Key to cancel.
ññññ130.25.36.8 PING Statisticsññññ
9 packets transmitted, 9 packets received, 0% packets loss
roundñtrip (ms) min/avg/max = 0/1/16
$
Abnormal Execution
$
ping 130.25.36.8
; Executes PING command
PING 130.25.36.8: 56 data bytes
←
Enter Ctrl+C Key to cancel.
ññññ130.25.36.8 PING Statisticsññññ
9 packets transmitted, 0 packets received, 100% packets loss
$
Refer to operating system documentation for your host computer for details
about using the host computer’s PING command.
9-3
Internode Test
The internode test sends data to and from specified nodes and uses the
responses to check the network.
If a normal response is returned for an internode test, it means that the set-
tings for the FL-net Unit are correct.
9-3-1
Running the Test
The test parameters are set and the test is started and stopped by writing the
required data to the CPU Bus Unit Area (in the CIO Area) of the PLC used to
start the internode test. These setting are made using a Programming Device,
such as a Programming Console.
Test Procedure
1,2,3...
1.
Write the test parameters into PLC memory. The test parameters are de-
scribed following this procedure.
2.
Turn ON the Internode Test Start Bit allocated to the FL-net Unit in the CPU
Bus Unit Area. The Internode Test Start Bit is described following the test
parameters. This will begin the internode test.
Summary of Contents for CJ1W-FLN22
Page 2: ......
Page 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 14: ...xiv...
Page 18: ...xviii...
Page 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Page 40: ...Precautions Section 1 6 14...
Page 50: ......
Page 88: ...Allocated Words in the DM Area Section 4 4 62...
Page 158: ...Command Response Reference Section 7 5 132...
Page 170: ......
Page 192: ...Inspections Section 10 6 166...
Page 218: ...192 System Configuration Appendix A...
Page 224: ...198 System Configuration Example Appendix B...
Page 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Page 276: ...250 International System of Units Appendix G...