CS/CJ-series Memory Areas and Virtual Addresses
Section 7-4
106
The MRES codes are shown in the following table along with the results they
indicate. Refer to
10-1 Troubleshooting with Indicators
for details on response
codes including the SRES.
7-4
CS/CJ-series Memory Areas and Virtual Addresses
Virtual address space is allocated in the Memory Area where messages are
read and written in FL-net (Ver. 2.00). The virtual address space in the Mem-
ory Area of all manufacturer’s FL-net (Ver. 2.00) nodes is allocated in 4-byte
hexadecimal within the virtual address space range, so you can read and
write between the Memory Areas of different equipment simply by specifying
the address.
The following table shows virtual address space allocation for OMRON PLCs
(CPU Units). Refer to the manual of other manufacturer’s FL-net (Ver. 2.00)
nodes for details on their virtual address space allocation.
Virtual Address Space for OMRON CS/CJ-series CPU Units
MRES
Execution results
00
Normal completion
01
Local node error
02
Remote node error
03
Unit error (controller error)
04
Service not supported
05
Routing error
10
Command format error
11
Parameter error
22
Status error
23
Operating environment error
25
Unit error
Area
Read/Write
Address
DM Area
D00000 to D32767
R/W
00020000 to 00027FFF
Timer Area
T000 to T4095
R/W
00090000 to 00090FFF
Counter Area
C000 to C4095
R/W
000A0000 to 000A0FFF
EM Area
Bank 0
E0_00000 to E0_32767
R/W
00200000 to 00207FFF
Bank 1
E1_00000 to E1_32767
R/W
00210000 to 00217FFF
Bank 2
E2_00000 to E2_32767
R/W
00220000 to 00227FFF
Bank 3
E3_00000 to E3_32767
R/W
00230000 to 00237FFF
Bank 4
E4_00000 to E4_32767
R/W
00240000 to 00247FFF
Bank 5
E5_00000 to E5_32767
R/W
00250000 to 00257FFF
Bank 6
E6_00000 to E6_32767
R/W
00260000 to 00267FFF
Bank 7
E7_00000 to E7_32767
R/W
00270000 to 00277FFF
Bank 8
E8_00000 to E8_32767
R/W
00280000 to 00287FFF
Bank 9
E9_00000 to E9_32767
R/W
00290000 to 00297FFF
Bank A
EA_00000 to EA_32767
R/W
002A0000 to 002A7FFF
Bank B
EB_00000 to EB_32767
R/W
002B0000 to 002B7FFF
Bank C
EC_00000 to EC_32767
R/W
002C0000 to 002C7FFF
CIO Area
0000 to 6143
R/W
00300000 to 003017FF
Work Area
W000 to W511
R/W
00310000 to 003101FF
Holding Area
H000 to H511
R/W
00320000 to 003201FF
Auxiliary Area
A000 to A447
R
00330000 to 003301BF
A448 to A959
RW
003301C0 to 003303BF
Summary of Contents for CJ1W-FLN22
Page 2: ......
Page 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 14: ...xiv...
Page 18: ...xviii...
Page 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Page 40: ...Precautions Section 1 6 14...
Page 50: ......
Page 88: ...Allocated Words in the DM Area Section 4 4 62...
Page 158: ...Command Response Reference Section 7 5 132...
Page 170: ......
Page 192: ...Inspections Section 10 6 166...
Page 218: ...192 System Configuration Appendix A...
Page 224: ...198 System Configuration Example Appendix B...
Page 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Page 276: ...250 International System of Units Appendix G...