205
Adjusting Offset and Gain
Section 5-7
CJ1W-DA021/041
The following diagram shows the flow of operations when using the adjust-
ment mode for adjusting offset and gain.
!Caution
Be sure to turn OFF the power to the PLC before changing the setting of the
operation mode switch.
Set the operation mode switch to adjustment mode
Turn ON the PLC and the external power supply.
When adjusting another output number
When adjusting the same output number
Set the output number.
Offset adjustment
Offset Bit ON
Set Bit ON
Turn OFF power to the PLC and the external power supply.
Set the operation mode switch to normal mode.
The ADJ indicator will flash while in adjustment mode.
Start up the PLC in PROGRAM mode.
Gain adjustment
Gain Bit ON
Output adjustment
Set Bit ON
Output adjustment
O
N
12
MODE
ON
OFF
O
N
12
MODE
ON
OFF
Set the operation mode switch on the DIP switch
on the back panel of the Unit to adjustment mode.
Write the output number to be adjusted
in the rightmost byte of CIO word n.
(Bit 0 of CIO word
n+1 turns ON.)
Adjustment
value setting
(Bits 2 and 3 of
CIO word n+1
turn ON.)
(Bit 4 of CIO word
n+1 turns ON.)
(Bit 1 of CIO word
n+1 turns ON.)
Adjustment
value setting
(Bits 2 and 3 of
CIO word n+1
turn ON.)
(Bit 4 of CIO word
n+1 turns ON.)
Set the operation mode switch on the DIP switch
on the back panel of the Unit to normal mode.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......